C: Using the IEC61850 Protocol Ethernet Network Server
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
• The nodes setTCTR1, setTCTR2, setTCTR3 and setTCTR4 contain the ratio of the
current used by the measuring device, for phases A,B,C and Neutral, respec-
tively. In this way, the user can take the IEC measurements (primary) and con-
vert them to Secondary using the ratios contained in these nodes.
• The nodes setTVTR1, setTVTR2 and setTVTR3 contain the ratio of the voltage
used by the measuring device.
• Any of the defined objects/ attributes can be placed within a dataset.
• The normal-speed in the Nexus® 1500+ meter is measurements taken every
second. The energy counters are also updated every second.
• The configuration of the devices takes place by converting the SCD file exported by
the System Configuration tool into a CID file. This CID file contains all of the infor-
mation from the SCD file which is needed for configuration by the EIG device. The
tool is named "SCDtoCIDConverter" and is a simple, publicly available program.
The resulting CID file is then sent to the EIG device using HTTP file transfer.