Doc
#
E154713
9-3
9: Network Communications
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1. From the Device Profile screen, double-click
General Settings> Communica-
tions
, then double-click on any of the ports. The Communications Settings screen
opens.
2. In the Network Settings section enter the following data.
NOTE:
The settings shown below are the default settings of the main Network
card. See Chapter 11 for the default settings of optional Network card 2.
• IP Address: 10.0.0.1
• Subnet Mask: 255.255.255.0
• Default Gateway: 0.0.0.0
NOTES
:
•You can use different settings for the main Network card (check with your
Network Administrator for the correct settings).
•We recommend that the main Network card and Network card 2 be in
different subnets, though this is not a necessity.
3. Once the above parameters have been set, Communicator EXT
TM
software connects
via the network using a Device Address of "1" and the assigned IP Address when
you follow these steps:
a. Open Communicator EXT
TM
software.
b. Click the
Connect
icon in the icon tool bar. The Connect screen opens.
c. Click the
Network
button at the top of the screen. Enter the following informa-
tion:
Device Address: 1
Host: The Network card’s IP Address
Network Port: 502
Protocol: Modbus TCP
d. Click the
Connect
button at the bottom of the screen. Communicator EXT
TM
software connects to the meter via the network.