Doc
#
E154713
11-8
11: Using the I/O Options
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
11.6: Relay Output Option Card (6RO1)
The Relay Output option card is used to send a control output (electrical signal) when
a limit is exceeded, for example to turn on a breaker or sound an alarm. The card has
6 relay contact outputs for load switching. The outputs are electrically isolated from
the main unit.
Accumulators in the Communicator EXT
TM
4.0 software count the transitions of the
outputs. When installing a Relay Output option card, we recommend you reset the
accumulators for the card, in order to prevent erroneous counts. See Chapter 20 of
the
Communicator EXT
TM
4.0 and MeterManager EXT Software User Manual
for
instructions on resetting the output accumulators.
The technical specifications at 25 °C are as follows:
Power consumption:
0.320 W internal
Relay outputs:
Number of outputs:
6
Contact type:
Changeover (SPDT)
Relay type:
Mechanically latching
Switching voltage:
AC 250 V / DC 30 V
Switching power:
1250 VA / 150 W
Switching current:
5 A
Switching rate max:
10/s
Mechanical life:
5 x 10
7
switching operations
Electrical life:
10
5
switching operations at rated
current
Breakdown voltage:
AC 1000 V between open contacts
Isolation:
AC 2500 V surge system to
contacts
Содержание Shark 100T