7: Transformer Loss Compensation
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Loss Compensation is applied to watt/VAR readings and, because of that, affects all
subsequent watt/VAR readings. This method results in loss compensation being
applied to the following quantities:
• Total power
• Demands, per phase and total (Block (Fixed) window and Rolling (Sliding) window)
• Maximum and minimum Demand
• Energy accumulations
• KYZ output of energy accumulations
The meter provides compensation for active and reactive power quantities by per-
forming numerical calculations. The factors used in these calculations are derived
either:
• By clicking the TLC Calculator button on the Transformer Loss screen of the Device
Profile, to open the EIG Loss Compensation Calculator in Microsoft Excel
• By figuring the values from the worksheet shown in “7.2.1.1: Three-Element Loss
Compensation Worksheet” on page 7, and in Appendix B of the
4.0 and MeterManager EXT Software User Manual
Either way, you enter the derived values into the Communicator EXT
TM
software
through the Device Profile Transformer and Line Loss Compensation screen.
The Communicator EXT
TM
software allows you to enable transformer loss compensa-
tion for losses due to copper and iron, individually or simultaneously. Losses can
either be added to or subtracted from measured readings. Refer to Appendix B in the
TM
4.0 and MeterManager EXT Software User Manual
for instruc-
tions.