11.8.9: Analog Input Modules
11.8.9.1: Overview
The Analog Input module converts a voltage level from a device, e.g., a temperature
or pressure meter, into a digital value that can be stored and processed in the meter.
The Analog Input Modules (0±1 mA, 0±20 mA, 0±5 VDC and 0±10 VDC) are avail-
able in 8-channel format. Maximum registers per request, read or write, is 17 regis-
ters.
All inputs share a single common point. This is also an isolated connection (from
ground).
Table 2:
Analog Input Module Specifications
Model Numbers
8AI1: 8-channel analog input 0±1 mA
8AI2: 8-channel analog input 0±20 mA
8AI3: 8-channel analog input 0±5 VDC
8AI4: 8-channel analog input 0±10 VDC
Accuracy
0.25% of Full Scale
Scaling
Programmable
Communication
RS485, Modbus RTU
Programmable Baud Rates: 4800, 9600, 19200,
38400, 57600
Power Requirement
12-20 VDC @50-200 mA; 1500+ supports up to four
modules
Operating Temperature
(-20 to +70)
o
C/(-4 to +158)
o
F
Maximum Load Impedance
0±1 mA: 10k Ohms; 4-20 mA: 500 Ohms
Factory Settings
Modbus Address: 8AI1: 136; 8AI2: 140; 8AI3: 144;
8AI4: 148
Baud Rate: 57600
Transmit Delay Time: 0
Default Settings (Reset Button)
Modbus Address: 247
Baud Rate: 57600
Transmit Delay Time: 20 msec