MANUAL ELDES ESIM264 V3.2
MANUAL ELDES ESIM264 V3.2
EKB3
Enter parameter 25, notification number and parameter status value:
25 061 #
Example:
25061#
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
21.2. Mains Power Status Monitoring
If the household electricity is unstable in the system installation area, the system may temporally lose its power supply and continue oper-
ating on the backup battery power. The system supervises the mains power supply and notifies the listed user phone number by SMS text
message as well as indicates system fault condition on the keypad (see
29. INDICATION OF SYSTEM FAULTS
) when the mains power
is lost. When the mains power restores, the system will notify the listed user phone number by SMS text message and the keypad will no
longer indicate system fault.
By default, system notification by SMS text message regarding mains power supply status is enabled. To disable/enable this notification,
please refer to the following configuration methods.
NOTE:
In case of low back-up battery, the system will send the SMS text message to the user and transmit the data message to the monitor-
ing station, but will NOT indicate a system fault on the keypad.
Disable mains power
loss notification
EKB2
Menu path:
OK
→
CONFIGURATION
→
OK
→
aaaa
→
OK
→
SMS MESSAGES
→
OK
→
MAIN PWR LOSS EV
→
OK
→
DISABLE
→
OK
Value:
aaaa
– 4-digit administrator password.
EKB3
Enter parameter 25, notification number and parameter status value:
25 04 0 #
Example:
25040#
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
Enable mains power
loss notification
EKB2
Menu path:
OK
→
CONFIGURATION
→
OK
→
aaaa
→
OK
→
SMS MESSAGES
→
OK
→
MAIN PWR LOSS EV
→
OK
→
ENABLE
→
OK
Value:
aaaa
– 4-digit administrator password.
EKB3
Enter parameter 25, notification number and parameter status value:
25 04 1 #
Example:
25041#
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
Disable mains power
restore notification
EKB2
Menu path:
OK
→
CONFIGURATION
→
OK
→
aaaa
→
OK
→
SMS MESSAGES
→
OK
→
MAIN PWR REST EV
→
OK
→
DISABLE
→
OK
Value:
aaaa
– 4-digit administrator password.
EKB3
Enter parameter 25, notification number and parameter status value:
25 05 0 #
Example:
25050#
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
Enable mains power
restore notification
EKB2
Menu path:
OK
→
CONFIGURATION
→
OK
→
aaaa
→
OK
→
SMS MESSAGES
→
OK
→
MAIN PWR REST EV
→
OK
→
ENABLE
→
OK
Value:
aaaa
– 4-digit administrator password.
EKB3
Enter parameter 25, notification number and parameter status value:
25 05 1 #
Example:
25051#
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
By default, mains power loss and restore delay are 30 and 120 seconds respectively. To set a different mains power loss and restore delay
duration, please refer to the following configuration methods.
Set mains power
loss delay
EKB2
Menu path:
OK
→
CONFIGURATION
→
OK
→
aaaa
→
OK
→
PRIMARY SETT INGS
→
OK
→
MAINS POWER
STATUS
→
OK
→
LOSS DELAY
→
OK
→
lllll
→
OK
Value:
aaaa
– 4-digit administrator password;
lllll
– mains power loss delay duration, range
- [0... 65535] seconds.
EKB3
Enter parameter 70 and loss delay duration:
70 lllll #
Value:
lllll
– mains power loss delay duration, range - [0... 65535] seconds.
Example:
7043#
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
Set mains power
restore delay
EKB2
Menu path:
OK
→
CONFIGURATION
→
OK
→
aaaa
→
OK
→
PRIMARY SETT INGS
→
OK
→
MAINS POWER
STATUS
→
OK
→
RESTORE DELAY
→
OK
→
rrrrr
→
OK
Value:
aaaa
– 4-digit administrator password;
rrrrr
– mains power restore delay duration,
range - [0... 65535] seconds.
EKB3
Enter parameter 71 and restore delay duration:
71 rrrrr #
Value:
rrrrr
– mains power restore delay duration, range - [0... 65535] seconds.
Example:
71150#
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
21.3. Memory
The configuration settings and event log records are stored in a built-in EEPROM memory, therefore even if the system is fully shut down,
the configuration and event log remain. For more details regarding the event log, please refer to
28. EVENT LOG
Содержание ESIM264
Страница 60: ...MadeintheEuropeanUnion www eldes lt...