RGK02
Operating Instructions
29
The maximum send duration is set to a value between 1 and 31 seconds in the parame-
ters. The standard value is 3 seconds. When receiving [1], the gateway starts transmit-
ting the send code and stops when receiving [0]. After expiration of the set maximum
send duration, the gateway automatically stops the transmission process.
ATTENTION!
During the transmission process, the gateway cannot process any other commands!
The transmission process is stopped by sending [0] to the deadman object. All incoming
KNX commands are buffered. At most eight commands can be buffered; if more com-
mands come in, these expire.
Easywave commands cannot be received during the entire transmission duration and
expire generally.