Product and functional description 

 

 

 

The instabus / DALI gateway N 141 is a KNX 

EIB

 device 

with one DALI output to which up to 64 DALI actuators 
(e.g. DALI ballasts) can be connected to. It is not allowed 
to connect DALI sensors to the output of the N 141. 
DALI (Digital Addressable Lighting Interface) is a 
bidirectional communications interface in accordance 
with IEC 60929, whose specification has been defined by 
manufacturers of electronic ballasts. It not only enables 
the receipt of e.g. switching and dimming commands but 
also the sending of status information such as the failure 
of a lamp or the report of a detected error in the 
electronic ballast. According to IEC 60929 up to 64 DALI 
devices can be connected to a DALI bus line and can each 
be assigned an individual device address.  
 
The instabus / DALI-Gateway N 141 can be used to 
control up to 64 DALI devices over the EIB. They can be 
switched and dimmed either individually or in groups. 
The N 141 also enables the detection and transmission of 
DALI status and failure information. An individual name, 
a group, scenes and parameters (refer to the application 
program description) are allocated to the individual DALI 
electronic ballasts during commissioning with the ETS 
(Engineering Tool Software). 
 
The power supply unit integrated in the N 141 supplies 
the gateway electronics and generates the DALI bus 
voltage. Additionally it enables the operation of the 
gateway and a direct switching of all lamps controlled 
over its DALI output even if the N 141 has not yet been 
commissioned with the ETS or if the communication via 
the EIB has been interrupted. For this purpose, the N 141 
has a pushbutton located bottom left on its front plate 

for switching On the “Direct mode” as well as for 
switching back to the “Bus mode”. When this pushbutton 
has been pressed for the first time the yellow LED lights 
up permanently to indicate direct mode. Then all lamps 
controlled over the DALI bus can be together switched 
On or Off via the relevant two pushbuttons on the front 
plate of the gateway such as via a bus pushbutton: 
pressing the upper pushbutton briefly switches the 
channel On while pressing the lower push button briefly 
switches the channel. A red LED integrated in the upper 
push button is used to indicate the state of the lamps by 
a continuous light and to indicate an error (e.g. a DALI 
bus, ballast or lamp failure) by flashing.  
If the direct mode button is pressed for a second time, 
the yellow LED to indicate direct mode is extinguished 
and the N 141 is switched to “Bus mode”. 
Note: If individual communication with each individual 
DALI device is not required and you wish for example to 
simply connect a group of dimmable fluorescent lamps in 
parallel and control them in the same way as you would 
previously have connected and controlled dimmable 
electronic control gear (ECG) with a 1...10 V interface, 
this is also possible with the switch/dimming actuator N 
525E. Status and error signals are also detected by the N 
525E and transmitted, whereby these signals are 
assigned to the respective group and not to an individual 
DALI device. 

 

Application program 

 

25 CO instabus / DALI Gateway 802701 

 

Summary of Contents for Instabus/DALI Gateway N 141

Page 1: ...pplies the gateway electronics and generates the DALI bus voltage Additionally it enables the operation of the gateway and a direct switching of all lamps controlled over its DALI output even if the N 141 has not yet been commissioned with the ETS or if the communication via the EIB has been interrupted For this purpose the N 141 has a pushbutton located bottom left on its front plate for switchin...

Page 2: ...EIB bus current 5 mA only half a standard bus load Electronics and DALI output integrated power supply for AC DC 110 240 V 50 400 Hz power consumption max 7 W Inputs outputs Mains connection 3 pole PE N L DALI output according to IEC 60929 max 64 DALI devices with 8 kOhm input impedance DALI bus voltage approx DC 19 V floating short circuit proof Operating elements 1 learning push button for toggl...

Page 3: ... A5 A7 A10 A9 A8 A6 Figure 1 Location of the display and operating elements A1 Button for toggling between normal addressing mode for transferring the physical address A2 LED red for displaying normal mode LED off or addressing mode LED on it is automatically extinguished once the physical address has been transferred A3 Plug for bus connecting terminal A4 Pushbuttons for direct operation all lamp...

Page 4: ...it reaches the stop Connecting the bus cable Figure 3 The bus terminal D2 is suitable for single core conductors with 0 6 0 8 mm Ø Strip approx 5 mm of insulation from the conductor D2 4 and plug in the terminal D2 red black Disconnecting the bus cable Figure 3 Remove the bus terminal D2 and the conductor D2 4 out of the bus cable by rotating it backwards and forwards D1 D2 D2 D2 4 D2 D2 4 5 mm D2...

Page 5: ...10 09 53 D 93009 Regensburg Subject to change without further notice 2 5 3 1 5 Figure 4 Covering the contact system Dimension drawing Dimensions in mm b 90 44 55 45 b 4 module units 1 module unit 18 mm General notes Any faulty devices should be returned to the local Siemens office If you have further questions about the product please contact our Technical Support 49 0 180 50 50 222 49 0 180 50 50...

Reviews: