RGK02
Operating Instructions
13
4
Functions and object properties
KNX programming and assignment of the Easywave radio products to the individual
objects (programming and deleting) is done with the ETS.
4.1
System objects
The three system objects are required for the administration of the Easywave send
codes. These objects are permanently integrated in the system and cannot be changed.
Valid group addresses must be assigned to use the system objects.
The following system objects are available:
641
(1 byte):
"Teach channel" (see chapter 4.1.1)
Teaching in a handheld transmitter on the memory slots 1-128
642
(1 byte):
"Delete channel" (see chapter 4.1.2)
Deleting a handheld transmitter on the memory slots 1-128
643
(1 bit):
"Delete all channels" (see chapter 4.1.3)
Deletes all programmed manual transmitters
After creating and assigning the group addresses, these can be addressed directly via
the ETS group monitor.