24
6 - COMBUSTION AIR AND VENT PIPING
FIGURE 6-5 - Two Pipe Polypropylene System
Adapter
FIGURE 6-6 - Separated Horizontal Flue Termination
Boiler
Note
If using indoor air for combustion do not exceed
100ft (30m) exhaust vent pipe.
Elbow
Total Length Reduction
45°
10" (0.3 m)
90°
2 ft (0.6 m)
Twin Pipe Maximum Vent Lengths (See Figure 6-6)
Intake Vent
L1
49 ft (15 m)
Exhaust Vent
L2
51 ft (15.5 m)
Combined Vent
L1+L2
100 ft (30.5 m)
Note
Do not count first elbow against maximum vent
length.
WARNING
Asphyxiation hazard! For Duravent polypropylene
twin pipe only. The twin pipe vent connections on
the 380 boiler are designed to accept 110 mm.
DuraVent polypropylene 4” venting measures 100
mm.
Manufacturer requires transition pieces from
Duravent to adapt from 110 mm to 100 mm. One
transition is required for the exhaust and one is
required for the fresh air intake.
Failure to follow these instructions could result in
death or serious injury.
!
WARNING
Asphyxiation hazard! Improper installation could
result in death or serious injury. Read Twin Pipe
Installation Instructions completely and understand
all requirements before beginning installation.
!
PN 240011662 Rev. H [04/30/2019]