80
13 - TROUBLE SHOOTING
Troubleshooting Chart 6
LP Installation?
NO
YES
Is gas shutoff valve fully
open?
NO
YES
Open Gas shutoff valve.
E36
- Burner Flame Loss
LP Conversion kit installed?
NO
YES
Has all air been purged
from gas line?
NO
YES
Replace
Spark
Generator
Install LP
Conversion Kit
Check all wires including
igniter and gas valve are
connected and tight.
NO
YES
Refer to section 6 of IOM and correct
vent terminations
Connect all wires assure secure fit.
Are ground wires
attached? Is boiler
properly grounded?
NO
YES
Provide proper ground.
Purge all air from gas line.
Check gas inlet pressure at least
equals rating plate requirements
NO
YES
Check gas line for obstructions
Check venting. Is
exhaust gas recirculating
to the air intake?
NO
YES
Clean or
Replace Igniter
Clear Vent
Obstruction
Remove igniter and
inspect. Is there damage
or contamination?
NO
YES
Restart boiler. Go to display
and check flame current. Is
there at least 3 mA?
NO
YES
Check venting for obstruction
and/or wind effects
NO
YES
Remove burner and inspect. Any
sign of damage to burner surface?
NO
YES
Replace
Burner
Check interior of heat exchanger for
debris or signs of blockage
NO
YES
Replace gas
valve
Clean Heat
Exchanger
PN 240011662 Rev. H [04/30/2019]