ZincBlue2 User Manual | 72
Settings Tab
The Settings tab has 6 subpages used to configure different aspects of a ZincBlue2.
Settings Tab
System Settings Page
The
System Settings
pages is used to configure several operating parameters of a ZincBlue2.
•
ZincBlue2 Name - Customize the name of the ZincBlue2. Each ZincBlue2 UPS 1000W/1500W is identified by an IP Address.
This dialog allows you to also create a name for the ZincBlue2 unit, such as a street address indicating geographical location
(e.g., "5th and Main"). The name can be up to 50 characters long, and there are no limitations on the characters you can use.
•
AC Thresholds - The high AC and low AC voltage thresholds set the upper and lower limits for acceptable input voltage to the
system. The default high AC voltage threshold is 130 volts and the default low AC threshold is 100 volts. If input voltage falls
outside of these limits, a power fail condition will be triggered, and the battery backup mode will be activated.
•
Line Qualifying Time - This setting specifies the required length of time after a power fail that the incoming AC power signal
must be within quality parameters before the system comes out of backup mode. The options for this setting are 3, 10, or 30
seconds. If the UPS detects unacceptable AC power quality within the line qualifying time period, the system will remain in
power fail mode and the line qualifying period starts over. The system will continue in this mode until the incoming power
quality is acceptable for the full line qualifying time.
•
Enable Tilt Switch - If enabled and the ZincBlue2 UPS 1000W/1500W exceeds 15 degrees from level, the devices Tilt Switch
will become active and will disable the battery bus. The ZincBlue2 UPS 1000W/1500W status screen will read TILT ERROR and
the red UPS FAULT status light will be on.
•
LCD Contrast – Adjust the contrast setting used for the front panel LCD of the UPS-1000W/1500W. The value is a percentage
from 0-100. The factory setting is 40. Changing the slider to the right, increases the contrast and changing the slider to the
left reduces the contrast. The SAVE button must be pressed in order for the new contrast value to be used. The saved contrast
value will be reused in the future if the UPS-1000W/1500W is ever rebooted.
Click the
Save
button to save settings changes. Click the
Cancel
button to discard changes.