ZincBlue2 User Manual | 48
STATUS
SETTINGS
EVENTS LIST
DEFINE EVENT
POWER FAILURE
Description:
Use this screen to enable or disable the utility power fail trigger. You can also specify a delay time after the power failure event
occurs before this event outcome is triggered.
On The Display:
•
POWER FAIL TRIGGER
: Allows you to turn on or off the Power Fail trigger or set a Power Resume trigger for when AC is re-
stored. Press the Navigation Dial to select an option, rotate the dial to select FAIL or RESUME or OFF and then press the dial to
set the value. By default, this trigger is set to OFF.
•
SET DELAY TIME:
Allows you to define a delay time, in hours, after a power failure before this trigger becomes TRUE. The delay
time is set in increments of 0.5 hours to a maximum of 8.0 hours. The default value, if none is specified, is 0.0 hours delay (that
is, the event outcome is triggered immediately upon utility power failure.)
•
Press the BACK button when you are finished configuring this trigger. You will be taken back to the DEFINE EVENT screen
where you can configure additional triggers for this relay, or complete configuration of a Power Failure event by going to the
RELAY screen to select a relay to perform that outcome and finalize the steps described in the EVENT SAVE CONFIRMATION
section of this manual.
Define Event: Power Failure
Edit Power Fail Trigger: Power Fail
Edit Power Fail Trigger: Power Resume
Edit Power Fail Trigger: Set Delay Time