25 | ZincBlue2 User Manual
Connecting Battery Panel or Battery Module to UPS and PIM
ONLY ZincFive batteries may be used with the UPS. Please refer to the UPS Overview for certified batteries.
To connect the battery to the UPS, follow these steps:
1. Connect the UPStealth 2 Battery Panel or Battery Module BATTERY OUTPUT to the BATTERY INPUT of the
UPStealth 2 UPS 1000W/1500W via the provided Digital and DC Power Interconnect Cable.
Note: If the Cold Start button is pressed upon connecting the Battery to the UPS, do not connect or disconnect
the Battery to or from the UPS until the green LED is off and Cold Start has expired. Press the Cold Start button
for 10 seconds to turn off the system.
2. Connect the UPStealth 2 Battery Panel or Battery Module AC INPUT to the TO BATTERY AC IN on the PIM using the
supplied Locking AC Power Interconnect Cable and AC Power Daisy Chain Cable as needed. When the battery unit is
connected to AC the battery unit LED should:
•
White Blinking = Battery at rest
•
Blue = Charging Mode
ONLY use the ZincFive provided interconnect cable
Note: When using a UPStealth 2 UPS 1500W it is a system requirement that two UPStealth 2 Battery Panels or
Battery Modules be used or a single UPStealth 2 XRT Battery 3600Wh. If not configured with the mentioned
batteries, the UPStealth 2 UPS 1500W will be in "BACKUP UNAVAILABLE" mode until the correct configuration is in
place.
Overtightening of these red twist locks may/can result in the cable being backed out of the connector.
Please pay specific attention to the installation instructions in the UPStealth 2 UPS User manual.
A1 - GND
A2 - B
Pins:
1. Can Bus (H)
2. Isolated CAN Bus GND
3. Can Bus (L)
4. 5V
5. Power Fail
~ 48Vdc
Digital and DC Power Interconnect Cable