Power Interface Module (PIM)
PIM Introduction
The Power Interface Module (PIM) provides an easy-to-connect interface
for incoming utility AC connecting to the UPS and the load.
The PIM provides an auto bypass function that enables the
technician to remove and service the UPS without shutting down
utility power. If, for any reason, the ouput of the ZincBlue2 UPS 1000W/1500W
is not available, then the PIM will automatically connect the load to the
utility line voltage.
PIM Overview
1. TO UPS AC IN
AC Input from PIM to UPS via the provided Locking AC Power Interconnect Cable.
2. FROM UPS AC OUT
AC Output from UPS to PIM via the provided Locking AC Power Interconnect Cable.
3. UPS TEST OUTPUT
Test output for the UPS. This output is always connected to the UPS output, regardless of Bypass Switch position.
4. CABINET LOAD
Connection points of the cabinet load to the PIM.
5. UTILITY INPUT
Connection points of AC power from the utility line to the PIM.
6. LOAD
20A breaker protection for the load.
7. UPS TEST
15A breaker/switch on incoming utility AC power.
•
In the ON position the AC from utility input is connected to the ZincBlue2 UPS 1000W/1500W providing power. The ZincBlue2 UPS
1000W/1500W is passing utility Input power through to the CABINET LOAD as well as the UPS TEST OUPUT on the PIM. No Battery
backup is used (assuming AC Utility power is present).
•
In the OFF position the AC from utility input is removed from the ZincBlue2 UPS 1000W/1500W and backup mode will be active.
Note: The UPS TEST switch is NOT used to check runtime as it does not disconnect AC POWER from the Battery Panel/Module.
8. BYPASS LIGHT
Will be lit when utility is directly connected to cabinet load.
9. TO BATTERY AC IN
ZincBlue2 Battery Panel/Module:
The connection between the PIM and Battery AC Input on the ZincBlue2 Battery Panel
or Module via the provided Locking AC Power Interconnect Cable.
ZincBlue2 XRT Battery 3600Wh:
The connection between the PIM and Battery AC INPUT on the ZincBlue2 XRT Battery
3600Wh IMS via the provided Locking AC Power Interconnect Cable.
Physical Characteristics
PIM
.................6”H x 10”W x 4”D 3.7 lbs.
PIM
4
1
2
3
5
6
7
8
9
Installation
Installation Safety
A battery can weigh up to 33 lbs. To avoid injury, use proper lifting techniques when unboxing and
installing.
UPS or battery(s) installation on a cabinet shelf or rack mount above your head is not recommended without
the use of properly staged ladders and assistance in lifting and placing the equipment.
Save the packaging material in the event a return is needed. Econolite does not warrant against product
damage from return shipping unless it is shipped in the original packaging.
The
ZincBlue2 system should be installed in a restricted access environment and only installed and serviced
by authorized personnel.
Tools Needed
• Slotted screwdriver
- (1/8” and 3/16”) 1/8” used for relay contact terminals. 3/16” used for utility and load
connections to PIM.
• Phillips screwdriver
- (#2) used for mounting the product.
• Flat head screwdriver -
Used for connecting the PIM terminals.
• Wire stripper
- Used for proper stripping of wires.
• Crimp tool
- Used for terminating ring lugs (not included) Termination to utility input and cabinet load are #8
screws.
• Voltage meter
- Used to check for voltage and to ensure proper connections.
• Socket wrench (10mm)
- Used to attach the DC Power Interconnect Cable to the monobloc nickel-zinc batteries.