ZincBlue2 User Manual | 46
STATUS
SETTINGS
EVENTS LIST
Description:
Use this screen to create new events or display or edit existing events. The ZincBlue2 UPS 1000W/1500W relay setup and trigger-
ing includes the ability to program Boolean AND as well as OR functions using a single relay.
To program AND functions:
Set up an Event as shown in the section DEFINE EVENT and assign it multiple triggers (between 2 and 4 triggers). Then assign the
Event to a Relay.
For example, Create Event 1 and assign the following 3 triggers including Power Fail, Time of Day and Battery Capacity %. Then,
assign that Event 1 to Relay 5. During UPS operation, If all the assigned triggers in the event are TRUE, (Trigger 1 AND Trigger 2
AND Trigger 3) then Relay 5 will be triggered. If only one or two of the assigned Event triggers are TRUE, then Relay 5 will not be
triggered.
To program OR functions:
Set up an Event as shown in the section DEFINE EVENT and assign it a single trigger. Then assign the Event to a Relay. Repeat this
process using an additional Event with a different trigger, then assign the Event to the same relay.
For example, Create Event 1 with a Power Fail trigger and assign that Event to Relay 4. Next, Create Event 2 with a Time Delay trig-
ger and assign that Event to Relay 4. If either Event #1 Power Fail OR Event #2 Time of Day is TRUE, then Relay 4 will be triggered. If
neither of the two Event triggers are TRUE, then Relay 4 will not be triggered.
On The Display:
•
Existing events (if any) are listed. Use the Navigation Dial to highlight an existing event and then press the dial to open it
for viewing or editing.
•
For each existing event, the relay used for the outcome is also listed.
•
DEFINE NEW EVENT:
Allows you to create a new event.
Notes:
You must use the ZincBlue2 Software to configure SMTP or SNMP outcomes.
Event List: No Events Defined
Event List: Events Defined