KGL Operating Manual – VS 3010 BS
2018-07-02
/
99 178
5. Analogue input for reading the analogue input signal of the FC / speed controller
Modern FCs / speed controllers often provide the possibility to output the actual speed or the motor current as
an analogue value. This analogue output must then be configured as a current output (4-20 mA) for this. The
analogue output signal of the Z1/Z2 FC / speed controller can then be applied at the analogue input for the
logging on the pack controller:
Compressor Z1: Analogue input 3 ((terminals 42/43)
Compressor Z2: Analogue input 5 (terminals 48/49)
5.5 Battery replacement
No battery replacement for the controller by the user is envisaged as the battery service life is designed for
greater than 10 years. If the "
" message is displayed, the controller must be sent to Eckelmann
battery voltage
AG to guarantee correct replacement of the battery. Opening the device is not authorised, see chapter
!
3010 BS Installation and start-up, page 84
Replacement of the battery after expiry of the warranty is subject to a charge.
The device contains a lithium battery (for details, see chapter
) that must be disposed of
separately!
Never dispose of this product with other domestic waste. Please inform yourself about the local regulations for the
separated disposal of electrical and electronic products and batteries. The correct disposal of your old equipment
protects the environment and people against possible negative consequences.
5.6 Firmware Update
The pack controller is delivered ready for operation with the current firmware. Future software versions can be
loaded into the pack controller as required using a firmware update, and thus updated.
Damage to the system and stock loss! Before the firmware update, the affected system component
or the system must be brought into a safe state as the shutdown of the controller during the firmware
update can have undesired effects on the system component and/or the system.