ANALOG VAL. ID: XXXXX
Display of the archived refrigeration point data in the store computer
Soll to Z2 T/N/A XX °C
Evaporating pressure setpoint for comparison Z2
CAN UA Z2
CAN bus address of the case controller in the Z2 circuit that increases the
t0-setpoint.
Only visible if "to-adjustment Z2" via consumer is activated.
Saug.temp.Z2
Suction gas superheat Z2
Ist üH Z2
Suction gas superheat Z2
Room temp. XX °C
Current room temperature (option)
Ist HD Z1 -/+/= X.XX b
Current condensation pressure Z1
Setp. HP Z1 W X.XX b
Setpoint condensation pressure Z1
Act. tc Z1 -/+/= XX °C
Current condensation temperature Z1
Setp.tc Z1 W XX °C
Setpoint condensation temperature Z1
Act. HP Z2 X.XX b
Current condensation pressure of the Z2 circuit during booster operation.
Only visible when high-pressure transducer in the Z2 circuit is activated
Act. tc Z2 XX °C
Current condensation pressure of the Z2 circuit during booster operation.
Only visible when high-pressure transducer in the Z2 circuit is activated
Setp. HP Z2 XX b
Setpoint condensation pressure Z2
Only visible when cascade controller is activated.
Setp. tc Z2 XX °C
Setpoint condensation pressure Z2
Only visible when cascade controller is activated.
Outdoor temp. XX °C
Current outdoor temperature (option)
Humidity XXX%
Current humidity
Cyl. temp. Z1 → Analogue cylinder temperature values, continue to
screen 2-1-a
Cyl. temp. Z2 → Analogue cylinder temperature values, continue to
screen 2-1-b
Speed Z1 XXX%
Compressor speed control variable for continuous compressor control Z1
Speed Z2 XXX%
Compressor speed control variable for continuous compressor control Z2
Speed HP XXX%
Fan speed control variable for continuous fan control
AnAusg.FU XXX%
Compressor speed for continuous compressor control Z1 read from
analogue input 3 of FC
COP Kühlb.Z1
COP value during cooling for Z1
COP HR Z1
COP value during HR mode for Z1
COP Carnot Z1
Averaged COP value with 2 NT refrigeration points (weighted with Carnot
factor Z1)
COP Kühlb.Z2
COP value during cooling for Z2
COP HR Z2
COP value during HR mode for Z2
COP Carnot Z2
Averaged COP value with 2 NT refrigeration points (weighted with Carnot
factor Z2)
Screen 2-1-a Cylinder head temperatures analogue values Z1
Z1-VERD.. ID: XXXXX
Cyl. temp. C1 XX °C
Cylinder head temperature display for first compressor
...
Only the actual number of compressors is displayed
Cyl. temp. Cn XX °C
Cylinder head temperature display for last Z1 compressor
Base module: max. number of total compressor stages: 4
with first SIOX extension module max. number of total compressor stages: 8
Z1 compressors: 1..n compressor stages: 1..max. 3/7, depending on system configuration