KGL Operating Manual – VS 3010 BS
2018-07-02
/
132 178
VS3010BS ID: XXX
7 Default settings
Continue to menu 7
8 Service Mode
Continue to menu 8
9.1.2 Menu 1 Overview
Ist to Z1 +/-/= XXX°C
Evaporating temperature actual value Z1
Soll to Z1 N/T/A XXX°C
Calculated t -setpoint evaporating temperature Z1
0
Ist to Z2 +/-/= XXX°C
Evaporating temperature actual value Z2
Soll to Z2 N/T/A XXX°C
Calculated t -setpoint evaporating temperature Z2
0
Ist tc Z1 +/-/= XXX°C
Condensation temperature actual value LP
Soll tc Z1 W XXX°C
Calculated t -setpoint condensation temperature HP
c
N = night operation
D = daytime operation
A = discharge gas defrosting setpoint active
W = heat recovery operation
9.1.3 Menu 2 Actual values
ACTUAL VALUES ID: xxxxx
1 Anal ogw.Verbund
Continue to menu 2-1
2 Compressors Z1
Continue to menu 2-2
3 Compressors Z2
Continue to menu 2-3
4 Fans
Continue to menu 2-4
5 System
Continue to menu 2-5
6 D2D *
Continue to menu 2-6
7 Cascade controll er **
Continue to menu 2-7
* Discharge gas defrosting only when this has also been activated, see chapter
Default settings with S1, page
.
** The function must be activated in menu 3-1.
Menu 2-1 Analogue values
ANALOG VAL. ID: XXXXX
Display of the archived refrigeration point data in the store computer
Ist ND Z1 +/-/= X.XX b
Current evaporating pressure Z1
Soll ND Z1 T/N/A X.XX b
Evaporating pressure setpoint Z1
Ist to Z1 +/-/= XX °C
Current evaporating temperature Z1
Soll to Z1 T/N/A XX °C
Evaporating temperature setpoint Z1
CAN UA Z1
CAN bus address of the case controller in the Z1 circuit that increases the
t0-setpoint.
Only visible if "to-adjustment Z1" via consumer is activated.
Saug.temp.Z1
Suction gas superheat Z1
Ist üH Z1
Suction gas superheat Z1
Ist ND Z2 +/-/= X.XX b
Current evaporating pressure Z2
Soll ND Z2 T/N/A X.XX b
Evaporating pressure setpoint for comparison Z2
Ist to Z2 +/-/= XX °C
Current evaporating temperature Z2