KGL Operating Manual – VS 3010 BS
2018-07-02
/
27 178
The characteristic of the frequency converter Z1/Z2 must be configurable for this so that an output signal of 0
V at the analogue output for compressor control corresponds to the minimum frequency and an output signal
of 10 V to the maximum frequency. The input signal of the frequency converter must be configured as 0 V – 10
V interface.
4.4.3.2 Loading / unloading of fixed-speed compressors during operation with capacity-controlled
compressors
Combined control operating mode with single-stage, fixed-speed compressors - parameter
=
M.com.out.reg.
No
(Z1 circuit: menu 3-2-1-1 / Z2 circuit: menu 3-2-1-2)
With capacity-controlled compressors, the additional capacity stage is only used for the speed controlled
compressor. The fixed-speed compressor is always operated at 100%.
The graphic shows the controller process of a compressor pack with 2 compressors with two-stage capacity
control.
The frequency converter must be configured for this so that an output signal of 0 V at the analogue output of
the controller corresponds to the minimum frequency and an output signal of 10 V to the maximum frequency.
The input signal of the frequency converter must be configured as 0 V..10 V interface.
Combined control with capacity-controlled fixed-speed compressors operating mode - parameter
M.com.out.