4 Commissioning
4.4 Cyclic data
DX-NET-SWD...
08/14 MN04012009Z-EN
www.eaton.com
45
1
0
OnOff
On/Off
0: Normal stop (with configured ramp time)
1: Operation
This bit needs to be toggled once in order to start operation. This bit will not start or
stop the device during normal operation.
1
Off2
Run-down (Coast Stop: Off 2)
0: Coast stop (switch off output voltage)
1: no free run-down
If this bit has a value of 0, the variable frequency drive/variable speed starter is
coasting and the output is de-energized. If it has a value of 1, the variable frequency
drive/variable speed starter is running normally. This bit will not start or stop the
device during normal operation.
2
Off3
Quick Stop: Off3
0: Quick stop (shortest ramp)
1: no quick stop
If this bit has a value of 0, the device will be stopped with a quick stop with the
shortest ramp time. If it has a value of 1, the variable frequency drive/variable speed
starter is running normally. This bit will not start or stop the device during normal
operation.
3
EN_Op
Operation released
0: Stop
1: Operation
If this bit has a value of 0, the variable frequency drive/variable speed starter will
stop. If it has a value of 1, the variable frequency drive's/variable speed starter's
output will be enabled. This bit will start and stop the device during normal
operation.
4
EN_Ramp
Release ramp (Enable Ramp Generator)
0: Reset ramp (setpoint value = 0)
1: Release ramp
If this bit has a value of 0, the variable frequency drive/variable speed starter will
remain stopped; the output will not be switched off. If it has a value of 1, the ramp
enable signal will be activated and the device will start with the set ramp.
5
Unfreeze
Unfreeze ramp
0: Freeze ramp (the ramp generator's current output value will be frozen)
1: Do not freeze ramp
If this bit has a value of 0, the variable frequency drive/variable speed starter will
continue running with the most recently set frequency; the output will not be
switched off. If this occurs after the ramp time elapses, this will have no effect until
the next setpoint change. If the bit has a value of 1, the device will continue running
along the set ramp all the way to the frequency setpoint.
6
EN_Set
Enable Setpoint
EN_Set enables the setpoint value and starts or stops the motor with the ramp
function.
0: Do not activate setpoint value
1: activate setpoint value
If this bit has a value of 0, the variable frequency drive/variable speed starter will
not receive a setpoint and will remain at the minimum frequency; the output will not
be switched off. If it has a value of 1, the setpoint will be activated.
7
FaultAck
Fault Acknowledge
0: Do not acknowledge current fault
1: Acknowledge current fault (rising edge: 0
→
1)
This bit can be used to reset a fault in the variable frequency drive/variable speed
starter. The fault acknowledge function will only respond to a rising edge, i.e., to the
value changing from 0 to 1.
2 - 3
0 - 15
Setpoint
Setpoint as a percentage
The setpoint is specified as an integer value between -100 % and 100 %:
100 %
≙
4000
hex
Byte
BIT
Designation
Meaning
Содержание Power XL SmartWire-DT DX-NET-SWD Series
Страница 4: ...II ...
Страница 10: ...0 About this Manual 0 7 Units of measurement 6 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 32: ...3 Installation 3 3 Install SmartWire DT connection 28 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 92: ...4 Commissioning 4 6 SmartWire DT diagnostics 88 DX NET SWD 08 14 MN04012009Z EN www eaton com ...