4 Commissioning
4.5 Acyclic data
80
DX-NET-SWD...
08/14 MN04012009Z-EN
www.eaton.com
SmartWire-DT read response(-) – Error
If an error has occurred, the read response will contain an error.
These errors are bus-specific and are explained in the corresponding
sections.
SmartWire-DT read re) – Parameter channel error
If there is an error in the parameter channel, a positive SmartWire-DT read
re) – Parameter channel error will be generated. The error will be
contained either in a write job or a read job.
The following table lists the PROFIdrive profile‘s parameter channel errors.
The possible errors for the variable frequency drive/variable speed starter are
marked (column „DA1, DC1, DE1“).
Table 17: Parameter channel errors with PROFIdrive
Byte
Designation
Description
0
Request Reference
Request identification: Is echoed
1
Response-ID
Response ID: 81
hex
: Read job(-); 82
hex
: Write job(-)
2
DO-ID
Drive-Object-ID: Is echoed
3
No. of Parameters
Number of Parameters: 01
hex
4
Format
Format: 44
hex
: Error
5
No. of Values
Number of values: 01
hex
6 - 9
Error Number
Fault number: 00
hex
– 23
hex
Fault
number
[hex]
Designation
Description
Supplemen-
tary infor-
mation
DA1
DC1
DE1
00
Invalid parameter number
Attempting to access a non-available
parameter
0
✓
01
Parameter value cannot be
changed
Attempting to have write access to a
parameter that cannot be modified
Subindex
✓
02
Value below lower limit or
above upper limit
Attempting to have write access with a value
outside the value range
Subindex
✓
03
Bad subindex
Attempting to access to a non-available
subindex in a string or array parameter
Subindex
✓
04
Not an array
Attempting to use a subindex in order to
access a parameter without index
0
–
05
Incorrect data type
Attempting to access a parameter with a
value not corresponding to the parameter's
data type
0
✓
06
Setting not allowed
Write access with a non-zero value not
allowed
Subindex
✓
07
Description element cannot be
modified
Attempting to have write access to a
description element that cannot be modified
Subindex
–
08
reserved
–
–
–
09
No description data available
Attempting to access a non-available
description. The value is not available.
0
✓
Содержание Power XL SmartWire-DT DX-NET-SWD Series
Страница 4: ...II ...
Страница 10: ...0 About this Manual 0 7 Units of measurement 6 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 32: ...3 Installation 3 3 Install SmartWire DT connection 28 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 92: ...4 Commissioning 4 6 SmartWire DT diagnostics 88 DX NET SWD 08 14 MN04012009Z EN www eaton com ...