4 Commissioning
4.4 Cyclic data
DX-NET-SWD...
08/14 MN04012009Z-EN
www.eaton.com
39
1
0
ERR
Error present
0: no error
1: Error
Indicates whether there is a variable frequency drive/variable speed starter
fault. If there is one, the device will respond as configured in PNU 362.0.
1
WARN
Warning present
0: no warning
1: Warning
Indicates whether there is a variable frequency drive/variable speed starter
warning.
2
RDY
Ready, switched on
0: not switched on
1: switched on
Indicates whether the variable frequency drive/variable speed starter is
switched on.
3
f = f-ref
operation at setpoint
0: Ref. frequency not reached
1: Ref. frequency reached
As long as the slip compensation is lower than 5%, this parameter will
have a value of 1. The bit's value will change to 0 for values higher than
5%.
• DC1, DE1: The bit will have a constant value of 1.
In the event of a fault, the value will change to 0.
• DA1: If the slip frequency is lower than 5%
([(P0-63)-(P0-60))/(P0-63] < 5%), the value will be 1. Otherwise, the
value will be 0.
4
f-Level
Actual speed is greater than the signalling threshold
0: Actual speed is less than or equal to the signaling threshold
1: Actual speed is greater than the signalling threshold
If the actual speed is greater than the value set on relay output 1, the value
will be 1. Otherwise, it will be 0.
• DC1, DE1: P00-03
≧
P-19
• DA1: Depending on the operating mode: P0-60 or P0-25
≧
P2-16
5
Q 1
Device Info Q1
The bit will have a value of 1 if the condition below is met; otherwise, it
will have a value of 0.
• DC1, DE1: The motor current is greater than the limit value –
comparable to the relay function if P-18 = 5.
• DA1: The motor's torque is greater than the limit value – comparable
to the relay function if P2-16 = 6.
6
Q2
Device Info Q2
Reserved – not used as of this writing
7
Q3
Device Info Q3
Reserved – not used as of this writing
Byte:
BIT
Designation
Meaning
Содержание Power XL SmartWire-DT DX-NET-SWD Series
Страница 4: ...II ...
Страница 10: ...0 About this Manual 0 7 Units of measurement 6 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 32: ...3 Installation 3 3 Install SmartWire DT connection 28 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 92: ...4 Commissioning 4 6 SmartWire DT diagnostics 88 DX NET SWD 08 14 MN04012009Z EN www eaton com ...