4.5 Acyclic data
DX-NET-SWD...
08/14 MN04012009Z-EN
www.eaton.com
81
0A
reserved
–
–
–
C0
No usage rights
Attempting to have write access without
write permissions
0
✓
0C
reserved
–
–
–
0D
reserved
–
–
–
0E
reserved
–
–
–
0F
No text array available
Attempting to access a non-available text
array
0
–
10
reserved
–
–
–
11
Request cannot be carried out
due to operating status
Access is temporarily not possible
0
✓
12
reserved
–
–
–
13
reserved
–
–
–
14
Value not permitted
Attempting to have write access with a value
that is within the value range, but that is not
permitted due to other reasons (parameter
with defined values)
Subindex
✓
15
Request too long for acyclic
communication channel
The length of the current request exceeds the
maximum permitted length of the acyclic
communication channel.
0
–
16
Parameter address not
permissible
Not permissible or non-supported value for
attribute, No. of elements, parameter number,
subindex, or a combination thereof
0
✓
17
Format not permissible
Write request: Invalid format or format not
permissible for this parameter
0
–
18
No. of values are not consistent
Write request: The number of values in the
parameter data does not match the number of
values for the parameter address.
0
–
19
DO does not exist
Attempting to access a non-existing drive
object
0
✓
20
Parameter text element cannot
be changed
Attempting to have write access to a
parameter text element without write
permissions
Subindex
21
Not permissible request ID
unsupported service
✓
22
Response too long for
parameter manager
The length of the current response exceeds
the parameter manager's parameter
processing capacity.
–
23
Multiple parameter access not
permissible
Is not supported.
✓
…-64
reserved
–
–
65-FF
manufacturer specific
–
–
Fault
number
[hex]
Designation
Description
Supplemen-
tary infor-
mation
DA1
DC1
DE1
Содержание Power XL SmartWire-DT DX-NET-SWD Series
Страница 4: ...II ...
Страница 10: ...0 About this Manual 0 7 Units of measurement 6 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 32: ...3 Installation 3 3 Install SmartWire DT connection 28 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 92: ...4 Commissioning 4 6 SmartWire DT diagnostics 88 DX NET SWD 08 14 MN04012009Z EN www eaton com ...