4 Commissioning
4.4 Cyclic data
40
DX-NET-SWD...
08/14 MN04012009Z-EN
www.eaton.com
4.4.5 Profile 1 (8 bit): Outputs (control)
Output bytes 0 and 1 (Short) are mapped as follows on SmartWire-DT.
Table 12: Profile 1: Output bytes 0 and 1
Byte 1 is only needed for internal, SWD-specific functions.
Byte:
BIT
Designation
Meaning
0
0
FWD
Start Reverse
A value of 1 will start the variable frequency drive/variable speed starter
in the clockwise operating direction.
1
REV
Start anticlockwise operation
A value of 1 will start the variable frequency drive/variable speed starter
in the anticlockwise operating direction.
2
EN_Op
Enable operation
0: Stop (immediate disconnection of the output)
1: Operation
If this bit has a value of 0, the variable frequency drive's/variable speed
starter's output will be switched off directly. To start the device, this bit
must be set to a value of 1 and the FWD or REV bit must be set to 1 as well.
3
FaultAck
Fault Acknowledge
0: Do not acknowledge current fault
1: Acknowledge current fault (rising edge: 0
→
1)
This bit can be used to reset a fault in the variable frequency drive/variable
speed starter. The fault acknowledge function will only respond to a rising
edge, i.e., to the value changing from 0 to 1.
4
I1
programmable input 1
Can be used to set one of four binary-coded fixed frequencies.
→
Table in I2
5
I2
programmable input 2
Can be used to set one of four binary-coded fixed frequencies.
6
I3
programmable input 3
Can be used to switch the setpoint input from a fixed frequency to an
analog input.
0: Setpoint provided with fixed frequency
1: Setpoint provided with analog input
7
I4
programmable input 4
Reserved – not used as of this writing
1
0 - 7
–
Reserved – not used as of this writing
I1
I2
Fixed
frequenc
y
0
0
FF1
1
0
FF2
0
1
FF3
1
1
FF4
Содержание Power XL SmartWire-DT DX-NET-SWD Series
Страница 4: ...II ...
Страница 10: ...0 About this Manual 0 7 Units of measurement 6 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 32: ...3 Installation 3 3 Install SmartWire DT connection 28 DX NET SWD 08 14 MN04012009Z EN www eaton com ...