4 Commissioning
4.4 Cyclic data
DX-NET-SWD...
08/14 MN04012009Z-EN
www.eaton.com
43
2
0
RSO
Ready For Switching On: S2
0: Not ready for switching on
1: Ready for switching on
If this bit has a value of 1, the variable frequency drive/variable speed
starter is ready to be switched on and has status 2.
1
RDY
Ready to operate; switched on: S3
0: not ready for operation
1: ready for operation
If this bit has a value of 1, the variable frequency drive/variable speed
starter is ready for operation and has status 3. This means that the device
can be switched on immediately.
2
EN
Enabled; operation: S4
0: Stop
1: Operation
If this bit has a value of 1, the variable frequency drive's/variable speed
starter's power section (IGBTs) is active.
3
ERR
Error present
0: no error
1: Error
Indicates whether there is a variable frequency drive/variable speed starter
fault.
If there is a fault, the variable frequency drive/variable speed starter will
respond as configured in PNU 362.0.
4
C_Stop
Free run-down, output de-energized (coast stop)
0: no free run-down
1: free run-down
If this bit has a value of 1, the variable frequency drive/variable speed
starter is coasting and the output is de-energized.
5
Q_Stop
Quick stop, shortest ramp
0: no quick stop
1: Quick stop
If this bit has a value of 1, the variable frequency drive/variable speed
starter is stopping with the shortest ramp and the output is not de-
energized.
6
SOI
Reclosing lockout (switching on inhibited: S1)
0: No switch-on inhibit
1: Switch-on inhibit
If this bit has a value of 1, the variable frequency drive/variable speed
starter is in reclosing lockout mode and cannot be started.
7
WARN
Warning present
0: no warning
1: Warning
Indicates whether there is a variable frequency drive/variable speed starter
warning.
3, 4
0 – 15
ActSpeed
actual speed
Provides the current speed as an integer value between -200% and 200%.
100 %
≙
4000
hex
Byte
BIT
Designation
Meaning
Содержание Power XL SmartWire-DT DX-NET-SWD Series
Страница 4: ...II ...
Страница 10: ...0 About this Manual 0 7 Units of measurement 6 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 32: ...3 Installation 3 3 Install SmartWire DT connection 28 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 92: ...4 Commissioning 4 6 SmartWire DT diagnostics 88 DX NET SWD 08 14 MN04012009Z EN www eaton com ...