4 Commissioning
4.4 Cyclic data
36
DX-NET-SWD...
08/14 MN04012009Z-EN
www.eaton.com
4.4.2 Simplified starting with profile 2
4.4.2.1 DOL starting in profile 2
Use the following settings (as hexadecimal values) for the command (output
bytes 0 and 1):
Table 7: Starting
Table 8: Stop with ramp
Table 9: Stop, with run-down
Table 10: Fault scenario
Setpoints set using output bytes 2 and 3 will be represented as integer
values. 100% equals 4000
hex
.
The operating direction is specified with a negative setpoint:
For example: -100%
≙
C000
hex
Actual values will be returned in the same format using input bytes 3 and 4.
Value
description
16#0000
Voltage on device and connection present.
16#047E
This command changes the drive to Ready, but it is still at a standstill.
16#047F
This changes it from Ready to RUN and it starts to move if a setpoint
value is set.
Value
description
16#047F
Running in operation.
16#046F
Performs the ramp stop.
16#047F
This will cancel the ramp stop, and the variable frequency drive/
variable speed starter will keep running.
Value
description
16#047F
Running in operation.
16#047E
Performs the uncontrolled stop.
16#047F
This will cancel the ramp stop, and the variable frequency drive/
variable speed starter will keep running.
Value
description
16#047F
A fault occurs during ongoing operation.
16#0507
Resets the variable frequency drive/variable speed starter
16#047F
Start after troubleshooting
Содержание Power XL SmartWire-DT DX-NET-SWD Series
Страница 4: ...II ...
Страница 10: ...0 About this Manual 0 7 Units of measurement 6 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 32: ...3 Installation 3 3 Install SmartWire DT connection 28 DX NET SWD 08 14 MN04012009Z EN www eaton com ...
Страница 92: ...4 Commissioning 4 6 SmartWire DT diagnostics 88 DX NET SWD 08 14 MN04012009Z EN www eaton com ...