4 Wiring with
4.12 Year Time Switch
142
Operating instructions
05/10 MN05013003Z-EN
www.eaton.com
4.12.7 Function of the year time switch
The year time switch can switch ranges, individual days, months, years or
combinations of all three.
4.12.7.1 Years
ON: 2002 to OFF: 2010 means:
Recurring interval, switch on at 00:00 2002-01-01 00:00 and off at 00:00
2011-01-01.
4.12.7.2 Months
ON: 04 to OFF: 10 means:
Recurring interval, switch on at 00:00 April 1, and off at 00:00 November 1.
4.12.7.3 Days
ON: 02 to OFF: 25 means:
Recurring interval, switch on at 00:00 on day 2 of the month and off at 00:00
day 26, i.e. after the set day has fully elapsed.
4.12.8 Year time switch for sample parameter configurations
4.12.8.1 Configuring the parameters for recurring intervals
Example 1: Selecting year range (1-channel)
The year time switch Y1 is required to switch on at 00:00 on January 1 2010
and stay on until 00:00 January 1 2012.
Figure 74:
Select year range
→
Avoid making incomplete entries. It hinders transparency and
leads to unwanted functions.
Circuit diagram display
Parameter settings of the year
time switch Y1
1/1
31/12
2009
2010
2011
2012
Y1-------
Ä
Q1
Y1 A
+
ON --.--.10
OFF --.--.11
Содержание easy500, easy700
Страница 1: ...Operating Instructions Control Relay 500 700 05 10 MN05013003Z EN replaces 05 04 AWB2528 1508GB...
Страница 4: ...II...
Страница 28: ...1 1 5 operating principles 24 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 54: ...2 Installation 2 8 Connecting bus systems 50 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 190: ...5 settings 5 10 Displaying device information 186 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 210: ...7 What Happens If 7 3 Event 206 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 234: ...9 Glossary of terms 230 Operating instructions 05 10 MN05013003Z EN www eaton com...