4 Wiring with
4.2 Working with contacts and relays
Operating instructions
05/10 MN05013003Z-EN
www.eaton.com
71
4.2.5 Checking the circuit diagram
easy contains a built-in measuring device enabling you to monitor the
switching states of contacts and relay coils during operation.
▶
Complete the small parallel connection and switch easy to RUN mode via
the main menu.
▶
Return to the circuit diagram display.
You are now unable to edit the circuit diagram.
The circuit diagram display performs two functions depending on the mode:
•
STOP: Creation of the circuit diagram
•
RUN: Power flow display
▶
Switch on I3.
In the power flow display, energized connections are thicker than non-
energized connections.
You can follow energized connections across all rungs by scrolling the display
up and down.
I2---
u
---
Ä
Q4
I3---
k
→
If you switch to the circuit diagram display and are unable to
modify a circuit diagram, first check whether easy is in STOP
mode.
I2---
U---
Ä
Q4
I3
---k
→
The power flow display will not show signal fluctuations in the
millisecond range. This is due to the inherent delay factor of
LCD displays.
Содержание easy500, easy700
Страница 1: ...Operating Instructions Control Relay 500 700 05 10 MN05013003Z EN replaces 05 04 AWB2528 1508GB...
Страница 4: ...II...
Страница 28: ...1 1 5 operating principles 24 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 54: ...2 Installation 2 8 Connecting bus systems 50 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 190: ...5 settings 5 10 Displaying device information 186 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 210: ...7 What Happens If 7 3 Event 206 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 234: ...9 Glossary of terms 230 Operating instructions 05 10 MN05013003Z EN www eaton com...