2 Installation
2.7 Expanding inputs/outputs .
48
Operating instructions
05/10 MN05013003Z-EN
www.eaton.com
2.7.2 Remote expansion
Remote expansion units can be installed and run up to 30 m away from the
basic unit.
Figure 36:
Connecting remote expansion units to easy
DANGER
The two-wire or multi-core cable between units must have the
necessary insulation voltage required for the installation
environment concerned. In the event of a fault (ground leakage,
short-circuit) serious damage or injury to persons may otherwise
occur.
A cable such as NYM0 with a rated operating voltage of
U
e
= 300/500 V AC is normally sufficient.
→
Terminals E+ and E- of the EASY200-EASY are protected
against short-circuits and polarity reversal.
Functionality is only ensured if "E+" is connected with "E+" and
"E-" with "E-".
E+ E–
E+ E–
EASY719-…
EASY721-…
EASY200-
EASY
EASY6…-RE
EASY6…-TE
U
e
= 300/500 V
EASY…-AC-…E
Содержание easy500, easy700
Страница 1: ...Operating Instructions Control Relay 500 700 05 10 MN05013003Z EN replaces 05 04 AWB2528 1508GB...
Страница 4: ...II...
Страница 28: ...1 1 5 operating principles 24 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 54: ...2 Installation 2 8 Connecting bus systems 50 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 190: ...5 settings 5 10 Displaying device information 186 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 210: ...7 What Happens If 7 3 Event 206 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 234: ...9 Glossary of terms 230 Operating instructions 05 10 MN05013003Z EN www eaton com...