4.4.5.1 Function of the Less than comparison
Parameter display and parameter set for Less than analog value comparator.
Circuit diagram with analog value comparator.
Figure 49:
Signal diagram of analog value comparator in Less than mode
1: actual value at I7
2: setpoint plus hysteresis value
3: setpoint
4: setpoint minus hysteresis
The N/O contact switches off when the actual value at I7 exceeds the setpoint
value plus hysteresis. If the actual value at I7 falls below the setpoint value, the
N/O contact switches on.
A1 LT
+
I1
I7
Æ
F1
+0
I2 0100
æ
F2 +0
OS +0
HY
0025
A1-------
Ä
Q1
→
The values
F1 +0
,
F2 +0
and
OS +0
were not defined. A
gain is not used with any values. No offset is used.