D64RPBH13 SERIES B1 GROUND FAULT RELAY 

 

Revision 2 
September, 2009 

Page 13 

 

 

Output Circuit breaker: 

 

   Contacts: 

Maximum UL rating: ............................................................... 3 A @ 250 V ac, resistive 

 

 

EN 60947-5-1 rating: .......................... 1 A @ 125 Vac, Utilization category AC-12 

 

 

Maximum fusing under EN 60947-5-1: .........................................................  10 A 

 
 

 

 

Endurance: ....................................................................Greater than 10,000 operations 

 

 

 

Dielectric strength .............................................................................. 500 V ac at 60 Hz 

 

 

 

Configuration .................................. Voltage free form "C" 1 N.O. - 1 N.C. (3 terminals) 

 
    

Operating Mode (Selected on DIPswitch 12) ......................................................................... Non-Failsafe 

 

Failsafe 

 

Inhibit Level (Enabled - Disabled selected on DIPswitch 11)

  

 

 

With C311CT current transformer 500:1 ratio ............................... 10 to 100 Amps 

 

 

With C311CT current transformer 10,000:1 ratio ............................... 200 to 2000 Amps 

 

 

(Based on selected Trip Level setting) 

 

 

Inhibit Time .......................................................................................................................... Instantaneous 

 
 

Functional Test.............. Continuous monitoring of the external CT’s connection; Open Circuit causes trip 

 
 

Local Test ................................................................................. Double click Push button on front of relay 

 

 

Causes a G/F trip by voltage injection onto the CT input circuitry 

 
 

Remote Test .......................... One press of SPST N.C. momentary contact Push button, 3 A @ 10 V ac 

 

 

Causes an external CT Open Circuit trip by opening up the connection to the CT 

 
 

Local Reset .............................................................................................Toggle Operated Circuit Breaker 

 
 

Reset mode ................................................................................................................................... Manual 

 

Ground Fault Circuit: 

 

 

Ground Fault Trip Delay ................................................................25 milliseconds - 1.00 Second 

 

 

Setting within Range ....................................................................... DIPswitches on front of relay 

 

 

Zone Grading Backup Delay ........................................................ 25 milliseconds – 1.00 Second 

 

 

Setting within Range ....................................................................... DIPswitches on front of relay 

 

 

Ground Fault Trip Current Level ................................................. 2.5 - 60 Amps (using 500:1 CT) 

 

 

 

50 - 1200 Amps (using 10,000:1 CT) 

 

 

Setting within Range ....................................................................... DIPswitches on front of relay 

 

 

Ground Fault Trip Inhibit Backup Delay ........................................................ Fixed at 1.2 Second 

 

 

Frequency Response Range ..................................................................................... 45 - 200 Hz 

 

Accuracy: 

 

 

 

Trip current ...................................................................................... ±15% including CT accuracy 

 

 

Trip current Repeat ............................................................................................................... ±1% 

 

 

Trip time .......................................... -2/+5 ms or ±2.5% of G/F Trip Delay, whichever is greater

1

 

                                           

 

1

 

The ground fault detection mechanism has a “thermal” behavior for greatly reduced noise sensitivity: the 

quoted delays are valid for sinusoidal currents exceeding the set point by > 10 times; for reduced current 
excursions the delay increases as follows: 

Current = 6 x set point:    

add 3 ms 

Current = 4 x set point:    

add 8 ms 

Current = 2 x set point:    

add 20 ms 

Current = 1.2 x set point: add 60 ms 

 

Содержание Cutler-Hammer D64 Series

Страница 1: ...40 45 50 55 60 10A 10A 10A 10A 10A 20A 20A 20A 20A 20A 20A 50A 50A 50A 50A 50A 50A 50A 100A 100A 100A 100A 100A 100A 100A RL 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400 450 500 550 600 700...

Страница 2: ...5 G F TEST RESET 9 2 5 1 G F TEST INTERNAL 9 2 5 2 G F TEST EXTERNAL 9 2 5 3 RESET 9 2 6 MEMORY AFTER LOSS OF CONTROL VOLTAGE 10 3 INSTALLATION INSTRUCTIONS 10 3 1 MOUNTING 10 3 1 1 THROUGH THE DOOR...

Страница 3: ...current exceeds the inhibit level the output circuit breaker trip will be inhibited until the ground fault current drops below the inhibit level A voltage operated circuit breaker with an external to...

Страница 4: ...are in the tripped state Terminals 11 14 open Terminals 11 12 closed Manual Reset The toggle of the circuit breaker must be placed in the Normal position to reset the contacts to the normal state aft...

Страница 5: ...ero sequence current transformers with a turns ratio of 500 1 With Inhibit Disabled under the same conditions the output circuit breaker will trip after the preset trip delay time The INHIBIT function...

Страница 6: ...o provide the desired delay before the output relay will trip when the ground fault TRIP LEVEL setting is reached or exceeded The setting should be selected to co ordinate with other ground fault devi...

Страница 7: ...ode DIPSWITCH SETTINGS TRIP INHIBIT MODE 11 L LEFT R RIGHT L DISABLED R ENABLED Factory Setting DIPSWITCH SETTINGS LEVELS WHEN USING C311CTs WITH 500 1 TURNS RATIO LEVELS WHEN USING C311CTs WITH 10 00...

Страница 8: ...being stored in non volatile memory remain valid The proper procedure to change settings is as follows 1 The dipswitches are placed in the new positions ignoring the blinking LEDs 2 Within 15 seconds...

Страница 9: ...use the indication to be updated in either case 2 5 G F TEST RESET 2 5 1 G F TEST INTERNAL Double clicking the built in RESET TEST pushbutton invokes a test which switches an AC voltage onto the proce...

Страница 10: ...g of the button 3 INSTALLATION INSTRUCTIONS Place the D64RPBH13 in a clean dry enclosure Try to keep the exposure to mechanical shock and vibration to a minimum The internal electronics have been enca...

Страница 11: ...screw clamp terminals rated 10 Amps 300 Volts Terminals will accept 26 12 AWG solid or stranded conductors The terminals are pull apart They have two 12 AWG screw clamps per pole with 90 and 180 orien...

Страница 12: ...r Toroidal C311CT9 A2 2 56 65 mm inside diameter Toroidal C311CT28 A2 1 1 28 mm inside diameter Toroidal with wire leads Zero Sequence Current Transformers with 10 000 1 ratio C311CT11 2 56 65mm insid...

Страница 13: ...ary contact Push button 3 A 10 V ac Causes an external CT Open Circuit trip by opening up the connection to the CT Local Reset Toggle Operated Circuit Breaker Reset mode Manual Ground Fault Circuit Gr...

Страница 14: ...ipping Weight 2 43 lbs 1 10 kg Applicable Standards EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environm...

Страница 15: ...Part 4 11 Voltage dips drops variations immunity EN 60947 5 1 Low voltage switchgear and controlgear Part 5 1 Control circuit devices and switching elements Electromechanical control circuit devices...

Страница 16: ...NG EQUIPMENT RELAY CLASS 1 CONTACT RATING 3A 250 VAC CT 1 CBCT SEE MANUAL FOR SET UP AND TEST INSTRUCTIONS PROD BATCH Nr P23509xxx MADE IN HOLLAND REMOTE TEST D64RPBH13 SER B1 L EN60947 5 1 EN61000 4...

Страница 17: ...74 Mounting Hole Dia 0 158 4 4 01 2 83 DOOR CUTOUT THROUGH THE DOOR MOUNTING 125 15 100 105 100 16 6 95 102 72 FIGURE 2 DIMENSIONS AND WEIGHTS OPEN WEIGHT 1 88 LBS 85KG PACKAGED WEIGHT 2 43 LBS 1 10...

Страница 18: ...ROL POWER ON NORMAL NORMAL 5 LOSS OF CONTROL POWER NORMAL TOGGLE TRIPS 6 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING NORMAL Time Delay TRIPPED Time Delay Time Delay NORMAL Time Delay TRIPPED Tim...

Страница 19: ...ion is made for external testing if required Refer to Figure 1 Select a momentary contact single pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac Connect as shown in Figure 1 When...

Отзывы: