PUB 50413 

 

D64RPBH13 SERIES B1 GROUND FAULT RELAY 

 

Revision 2 
September, 2009 

Page 12 

 

 

Connect the external C311CT current transformer to terminal CT1 & CT2 of the D64RPBH13, using 14 
AWG (minimum) twisted conductors. If a remote Test button is being used connect as shown in Figure 
1. 

 

 

CAUTION: Internally these terminals are connected to the FB terminal via a 2.5 V DC voltage 
source, shunted with a 7 V transients suppressing zener diode. DO NOT connect the external 
transformer to ground at any other point.

 

4. 

CATALOG NUMBERS 

 

D64RPBH13 

Ground Fault Relay with 110 - 240 Volt ac/dc control voltage, for use on maximum 
660 Volt power system, current trip range: 2.5 – 60 Amps with 500:1 ratio C311CTs or 
50 - 1200 Amps with 10,000:1 ratio C311CTs, trip time: 25 ms – 1.0 sec, trip output: 
toggle operated circuit breaker, for use with service protection equipment.  

 

Zero Sequence Current Transformers with 500:1 ratio: 

 

C311CT1-A2 

1.81" (46 mm) inside diameter, Toroidal 

 

C311CT2-A2 

3.54" (90 mm) inside diameter, Toroidal 

 

C311CT3-A2 

5.9" x 6.7" (150 x 170 mm) rectangular, Split Core 

 

C311CT4-A2 

3.94" x 13.78" (100 x 350 mm) rectangular, Split Core 

 

 

C311CT5-A2 

5.7" (145 mm) inside diameter, Toroidal 

 

C311CT6-A2 

9.45" (240 mm) inside diameter, Toroidal 

 

C311CT7-A2 

11.8" x 11.8" (300 x 300 mm) square, Split core 

 

C311CT8-A2 

1.1" (28 mm) inside diameter, Toroidal 

 

C311CT9-A2 

2.56" (65 mm) inside diameter, Toroidal 

 

C311CT28-A2  1.1” (28 mm) inside diameter, Toroidal – with wire leads 

 

Zero Sequence Current Transformers with 10,000:1 ratio: 

 

C311CT11 

2.56” (65mm) 

inside diameter, Toroidal

  

 

C311CT12 

5.7" (144mm) 

inside diameter, Toroidal

  

 

C311CT13 

9.45" (238mm) 

inside diameter, Toroidal

  

 

C311CT14 

3.75" (95mm) 

inside diameter, Toroidal

  

 

C311CT15 

7.875" x 11.42” (200 x 290 mm) rectangular 

 
 

For mounting dimensions and additional information on C311CT current transformers refer to the 
current Eaton’s Cutler-Hammer catalog. 

 
 

The D64RPBH13 is designed to operate with special Eaton’s Cutler-Hammer C311CT current 
transformers having a turns ratio of 10,000:1. Each C311CT is epoxy molded for exceptional 
mechanical properties and has a high-grade silicon iron core for excellent coupling characteristics. 
C311CTs have built-in back-to-back zeners across the output terminals to provide maximum safety in 
the event of an open CT secondary circuit. 

 
 

NOTE: 

For Ground Fault Relay with programmable output relay and with zone grading option, 
suitable for use with service protection equipment; refer to D64RPBH15, Pub 50414. 

5. 

TECHNICAL SPECIFICATION

  

 

Control voltage .......................................................................  110 - 240 Volts 45 - 450 Hz AC, 2 VA max 

 

 

110 – 240 V dc, 1 W max 

 
 

Operating tolerance ............................................................................... 55% to 110% of rated ac voltage 

 

 

80% to 110% of rated dc voltage 

 
 

Maximum System Voltage & Frequency .......................................................... 660 Volts ac, 40 to 200 Hz 

 
 

The D64RPBH15 may be applied on higher voltage circuits providing the power conductors are 
insulated for the system voltage.  

Содержание Cutler-Hammer D64 Series

Страница 1: ...40 45 50 55 60 10A 10A 10A 10A 10A 20A 20A 20A 20A 20A 20A 50A 50A 50A 50A 50A 50A 50A 100A 100A 100A 100A 100A 100A 100A RL 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400 450 500 550 600 700...

Страница 2: ...5 G F TEST RESET 9 2 5 1 G F TEST INTERNAL 9 2 5 2 G F TEST EXTERNAL 9 2 5 3 RESET 9 2 6 MEMORY AFTER LOSS OF CONTROL VOLTAGE 10 3 INSTALLATION INSTRUCTIONS 10 3 1 MOUNTING 10 3 1 1 THROUGH THE DOOR...

Страница 3: ...current exceeds the inhibit level the output circuit breaker trip will be inhibited until the ground fault current drops below the inhibit level A voltage operated circuit breaker with an external to...

Страница 4: ...are in the tripped state Terminals 11 14 open Terminals 11 12 closed Manual Reset The toggle of the circuit breaker must be placed in the Normal position to reset the contacts to the normal state aft...

Страница 5: ...ero sequence current transformers with a turns ratio of 500 1 With Inhibit Disabled under the same conditions the output circuit breaker will trip after the preset trip delay time The INHIBIT function...

Страница 6: ...o provide the desired delay before the output relay will trip when the ground fault TRIP LEVEL setting is reached or exceeded The setting should be selected to co ordinate with other ground fault devi...

Страница 7: ...ode DIPSWITCH SETTINGS TRIP INHIBIT MODE 11 L LEFT R RIGHT L DISABLED R ENABLED Factory Setting DIPSWITCH SETTINGS LEVELS WHEN USING C311CTs WITH 500 1 TURNS RATIO LEVELS WHEN USING C311CTs WITH 10 00...

Страница 8: ...being stored in non volatile memory remain valid The proper procedure to change settings is as follows 1 The dipswitches are placed in the new positions ignoring the blinking LEDs 2 Within 15 seconds...

Страница 9: ...use the indication to be updated in either case 2 5 G F TEST RESET 2 5 1 G F TEST INTERNAL Double clicking the built in RESET TEST pushbutton invokes a test which switches an AC voltage onto the proce...

Страница 10: ...g of the button 3 INSTALLATION INSTRUCTIONS Place the D64RPBH13 in a clean dry enclosure Try to keep the exposure to mechanical shock and vibration to a minimum The internal electronics have been enca...

Страница 11: ...screw clamp terminals rated 10 Amps 300 Volts Terminals will accept 26 12 AWG solid or stranded conductors The terminals are pull apart They have two 12 AWG screw clamps per pole with 90 and 180 orien...

Страница 12: ...r Toroidal C311CT9 A2 2 56 65 mm inside diameter Toroidal C311CT28 A2 1 1 28 mm inside diameter Toroidal with wire leads Zero Sequence Current Transformers with 10 000 1 ratio C311CT11 2 56 65mm insid...

Страница 13: ...ary contact Push button 3 A 10 V ac Causes an external CT Open Circuit trip by opening up the connection to the CT Local Reset Toggle Operated Circuit Breaker Reset mode Manual Ground Fault Circuit Gr...

Страница 14: ...ipping Weight 2 43 lbs 1 10 kg Applicable Standards EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environm...

Страница 15: ...Part 4 11 Voltage dips drops variations immunity EN 60947 5 1 Low voltage switchgear and controlgear Part 5 1 Control circuit devices and switching elements Electromechanical control circuit devices...

Страница 16: ...NG EQUIPMENT RELAY CLASS 1 CONTACT RATING 3A 250 VAC CT 1 CBCT SEE MANUAL FOR SET UP AND TEST INSTRUCTIONS PROD BATCH Nr P23509xxx MADE IN HOLLAND REMOTE TEST D64RPBH13 SER B1 L EN60947 5 1 EN61000 4...

Страница 17: ...74 Mounting Hole Dia 0 158 4 4 01 2 83 DOOR CUTOUT THROUGH THE DOOR MOUNTING 125 15 100 105 100 16 6 95 102 72 FIGURE 2 DIMENSIONS AND WEIGHTS OPEN WEIGHT 1 88 LBS 85KG PACKAGED WEIGHT 2 43 LBS 1 10...

Страница 18: ...ROL POWER ON NORMAL NORMAL 5 LOSS OF CONTROL POWER NORMAL TOGGLE TRIPS 6 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING NORMAL Time Delay TRIPPED Time Delay Time Delay NORMAL Time Delay TRIPPED Tim...

Страница 19: ...ion is made for external testing if required Refer to Figure 1 Select a momentary contact single pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac Connect as shown in Figure 1 When...

Отзывы: