D64RPBH13 SERIES B1 GROUND FAULT RELAY 

 

Revision 2 
September, 2009 

Page 11 

 

3.2 

EXTERNAL C311CT CURRENT TRANSFORMER

 

 

The D64RPBH13 is designed to operate with either, a special Eaton’s Cutler-Hammer C311CT zero 
sequence current transformer with a turns ratio of 10000:1 or, the standard family of C311CT zero 
sequence current transformers with a turns ratio of 500:1. Each C311CT is epoxy molded for 
exceptional mechanical properties and has a high-grade silicon iron core for excellent coupling 
characteristics. C311CTs have built-in back-to-back zeners across the output terminals to provide 
maximum safety in the event of an open CT secondary circuit.    

 

Refer to section 4 to select the catalog number of the C311CT current transformer with the opening 
required for the application. . Each C311CT is epoxy molded for exceptional mechanical properties and 
has a high-grade silicon iron core for excellent coupling characteristics. C311CTs have built-in back-to-
back zeners across the output terminals to provide maximum safety in the event of an open CT 
secondary circuit. 

 

Phase conductors must be insulated for the system voltage when it is higher than 660 Volts.  

 

Refer to Figure 1. Pass the phase conductors through the CT window. If the neutral conductor is being 
connected downstream, it is to be passed through the window. Do not pass ground conductors through 
the CT window. In applications that require shielded wires to pass through the CT window, return the 
shields through the CT window before connecting them to ground.  

 
 

Position power cables in the center of the current transformer opening. Keep cables and buswork clear 
of the split on split core current transformers. 

3.3 

CONNECTIONS

 

 

All connections to the D64RPBH13 are by means of screw clamp terminals rated 10 Amps, 300 Volts. 
Terminals will accept #26-12 AWG solid or stranded conductors.  

 

The terminals are pull apart. They have two 12 AWG screw clamps per pole with 90

°

 and 180

°

 

orientation. A screw mounted locking block is located at each end of the terminal block for maximum 
security.   

 

Since the relay housing is non metallic, no chassis bond is required. 

 

For good EMC behaviour the following wiring practices are recommended: 

Connect the FB (“Frame Bond”) terminal to the structure ground as close as practically 
possible to the component being grounded using the shortest wire. 

The D64RPBH13 has an isolated power supply. Therefore the N- terminal should be 
connected to the structure ground at the same point as the neutral of the control 
transformer. See figure 1. 

Avoid looping or coiling any/all wires connected to the component. 

Dress all conductors as close as practically possible to the back panel or grounded 
frame. 

Use shielded twisted leads on interconnection between CT and Relay.  

The shield should extend the full length of the twisted interconnection leads. 

Connect shield to structure ground as close as practically possible to the Relay. 

When stripping conductor insulation care should be taken to avoid breaking any 
conductor strands. 

 

Connect 110-240 Volt ac/dc control voltage to terminals L+ & N-. 

 

Refer to Figure 1 and Table 4. Decide on the connection of field devices to output circuit breaker 
contact terminals by comparing the desired control of the field devices under various operating 
conditions. 

 

Figure 1 shows a typical connection of a 120 Volt ac circuit breaker shunt trip coil (ST) to the closed 
contact of the output circuit breaker. Comparing the output circuit breaker contact states, it can be seen 
that this could be used with the NON-FAILSAFE operating mode. The N.C. contact, terminals 11 & 12, 
(open when the circuit breaker toggle is placed in the NORMAL position) would be used for the shunt 
trip coil circuit. 

Содержание Cutler-Hammer D64 Series

Страница 1: ...40 45 50 55 60 10A 10A 10A 10A 10A 20A 20A 20A 20A 20A 20A 50A 50A 50A 50A 50A 50A 50A 100A 100A 100A 100A 100A 100A 100A RL 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400 450 500 550 600 700...

Страница 2: ...5 G F TEST RESET 9 2 5 1 G F TEST INTERNAL 9 2 5 2 G F TEST EXTERNAL 9 2 5 3 RESET 9 2 6 MEMORY AFTER LOSS OF CONTROL VOLTAGE 10 3 INSTALLATION INSTRUCTIONS 10 3 1 MOUNTING 10 3 1 1 THROUGH THE DOOR...

Страница 3: ...current exceeds the inhibit level the output circuit breaker trip will be inhibited until the ground fault current drops below the inhibit level A voltage operated circuit breaker with an external to...

Страница 4: ...are in the tripped state Terminals 11 14 open Terminals 11 12 closed Manual Reset The toggle of the circuit breaker must be placed in the Normal position to reset the contacts to the normal state aft...

Страница 5: ...ero sequence current transformers with a turns ratio of 500 1 With Inhibit Disabled under the same conditions the output circuit breaker will trip after the preset trip delay time The INHIBIT function...

Страница 6: ...o provide the desired delay before the output relay will trip when the ground fault TRIP LEVEL setting is reached or exceeded The setting should be selected to co ordinate with other ground fault devi...

Страница 7: ...ode DIPSWITCH SETTINGS TRIP INHIBIT MODE 11 L LEFT R RIGHT L DISABLED R ENABLED Factory Setting DIPSWITCH SETTINGS LEVELS WHEN USING C311CTs WITH 500 1 TURNS RATIO LEVELS WHEN USING C311CTs WITH 10 00...

Страница 8: ...being stored in non volatile memory remain valid The proper procedure to change settings is as follows 1 The dipswitches are placed in the new positions ignoring the blinking LEDs 2 Within 15 seconds...

Страница 9: ...use the indication to be updated in either case 2 5 G F TEST RESET 2 5 1 G F TEST INTERNAL Double clicking the built in RESET TEST pushbutton invokes a test which switches an AC voltage onto the proce...

Страница 10: ...g of the button 3 INSTALLATION INSTRUCTIONS Place the D64RPBH13 in a clean dry enclosure Try to keep the exposure to mechanical shock and vibration to a minimum The internal electronics have been enca...

Страница 11: ...screw clamp terminals rated 10 Amps 300 Volts Terminals will accept 26 12 AWG solid or stranded conductors The terminals are pull apart They have two 12 AWG screw clamps per pole with 90 and 180 orien...

Страница 12: ...r Toroidal C311CT9 A2 2 56 65 mm inside diameter Toroidal C311CT28 A2 1 1 28 mm inside diameter Toroidal with wire leads Zero Sequence Current Transformers with 10 000 1 ratio C311CT11 2 56 65mm insid...

Страница 13: ...ary contact Push button 3 A 10 V ac Causes an external CT Open Circuit trip by opening up the connection to the CT Local Reset Toggle Operated Circuit Breaker Reset mode Manual Ground Fault Circuit Gr...

Страница 14: ...ipping Weight 2 43 lbs 1 10 kg Applicable Standards EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environm...

Страница 15: ...Part 4 11 Voltage dips drops variations immunity EN 60947 5 1 Low voltage switchgear and controlgear Part 5 1 Control circuit devices and switching elements Electromechanical control circuit devices...

Страница 16: ...NG EQUIPMENT RELAY CLASS 1 CONTACT RATING 3A 250 VAC CT 1 CBCT SEE MANUAL FOR SET UP AND TEST INSTRUCTIONS PROD BATCH Nr P23509xxx MADE IN HOLLAND REMOTE TEST D64RPBH13 SER B1 L EN60947 5 1 EN61000 4...

Страница 17: ...74 Mounting Hole Dia 0 158 4 4 01 2 83 DOOR CUTOUT THROUGH THE DOOR MOUNTING 125 15 100 105 100 16 6 95 102 72 FIGURE 2 DIMENSIONS AND WEIGHTS OPEN WEIGHT 1 88 LBS 85KG PACKAGED WEIGHT 2 43 LBS 1 10...

Страница 18: ...ROL POWER ON NORMAL NORMAL 5 LOSS OF CONTROL POWER NORMAL TOGGLE TRIPS 6 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING NORMAL Time Delay TRIPPED Time Delay Time Delay NORMAL Time Delay TRIPPED Tim...

Страница 19: ...ion is made for external testing if required Refer to Figure 1 Select a momentary contact single pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac Connect as shown in Figure 1 When...

Отзывы: