manualshive.com logo in svg
background image

 

 

 

 

 

PUB 50413 

 

D64RPBH13 SERIES B1 GROUND FAULT RELAY 

 

Revision 2 
September, 2009 

Page 8 

 

2.2.4 

OUTPUT CIRCUIT BREAKER OPERATING MODE –CONTACT STATE 

The two different OPERATING MODES are described under the glossary of terms. The setting of 
DIPswitch 12 determines the operating mode of the D64RPBH13 output circuit breaker. This is shown 
in Table 4. Use this table when deciding on field connections. The state of the output circuit breaker 
contacts is shown in Table 5. Also, refer to the CONNECTIONS section.  
 

Table 4: Output Circuit Breaker Operating Mode 

 

DIPSWITCH 

SETTINGS 

OUTPUT CIRCUIT 

BREAKER 

OPERATING MODES 

12 

L=LEFT 

R=RIGHT 

NON-FAILSAFE 

FAILSAFE 

* Factory Setting 

 

2.3 

TAMPER PROOF DIPSWITCHES

 

 

Eleven of the twelve DIPswitches are used to program the D64RPBH13. However, to discourage 
unauthorized manipulation, the preselected settings can only be changed by going through the 
procedure outlined below. 

 
 

When an attempt is made to change the settings without going through this procedure, the green and 
red LEDs start to blink alternately until the switches are returned to their original positions. Should the 
switches be left in other than the preselected settings, the preselected settings, being stored in non-
volatile memory, remain valid. 

 
 

The proper procedure to change settings is as follows: 

 

1. 

The dipswitches are placed in the new positions (ignoring the blinking LEDs). 

2. 

Within 15 seconds after the last change was made (or control power was applied), the system 
is brought in test mode using the local pushbutton, causing the new settings to become active. 
Since the system will trip now, changing the settings cannot go by undetected. See section 2.5 
for a description of how to invoke test mode. 

Note that any trips must be reset before this procedure can be completed. 

 

2.4 

INDICATION

 

 

There are two LED’s on the front of the D64RPBH13.  

 

A green RUN LED shows correct operation by slowly flashing (1 s on/ 1 s off) when control 
voltage is applied to terminals L+ & N-.  

  

A red LAST TRIP LED shows short 0.25 s flashes as a code indicating the cause of LAST 
TRIP:  

One flash every few seconds means that the ground fault current exceeded the set 
G/F Trip Level during the G/F Trip Delay time.. In case the G/F Trip Inhibit function is 
enabled, the ground fault current may have exceeded the Trip Inhibit Level (overriding 
the G/F Trip Delay time), but in that case the upstream tripping device tripped correctly 
within 1.2 s and after the current dropped to zero as a result of that, the D64RPBH13 
activated its output circuit breaker to isolate the faulty circuit. This trip is labelled 
Ground Fault. 

Содержание Cutler-Hammer D64 Series

Страница 1: ...40 45 50 55 60 10A 10A 10A 10A 10A 20A 20A 20A 20A 20A 20A 50A 50A 50A 50A 50A 50A 50A 100A 100A 100A 100A 100A 100A 100A RL 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400 450 500 550 600 700...

Страница 2: ...5 G F TEST RESET 9 2 5 1 G F TEST INTERNAL 9 2 5 2 G F TEST EXTERNAL 9 2 5 3 RESET 9 2 6 MEMORY AFTER LOSS OF CONTROL VOLTAGE 10 3 INSTALLATION INSTRUCTIONS 10 3 1 MOUNTING 10 3 1 1 THROUGH THE DOOR...

Страница 3: ...current exceeds the inhibit level the output circuit breaker trip will be inhibited until the ground fault current drops below the inhibit level A voltage operated circuit breaker with an external to...

Страница 4: ...are in the tripped state Terminals 11 14 open Terminals 11 12 closed Manual Reset The toggle of the circuit breaker must be placed in the Normal position to reset the contacts to the normal state aft...

Страница 5: ...ero sequence current transformers with a turns ratio of 500 1 With Inhibit Disabled under the same conditions the output circuit breaker will trip after the preset trip delay time The INHIBIT function...

Страница 6: ...o provide the desired delay before the output relay will trip when the ground fault TRIP LEVEL setting is reached or exceeded The setting should be selected to co ordinate with other ground fault devi...

Страница 7: ...ode DIPSWITCH SETTINGS TRIP INHIBIT MODE 11 L LEFT R RIGHT L DISABLED R ENABLED Factory Setting DIPSWITCH SETTINGS LEVELS WHEN USING C311CTs WITH 500 1 TURNS RATIO LEVELS WHEN USING C311CTs WITH 10 00...

Страница 8: ...being stored in non volatile memory remain valid The proper procedure to change settings is as follows 1 The dipswitches are placed in the new positions ignoring the blinking LEDs 2 Within 15 seconds...

Страница 9: ...use the indication to be updated in either case 2 5 G F TEST RESET 2 5 1 G F TEST INTERNAL Double clicking the built in RESET TEST pushbutton invokes a test which switches an AC voltage onto the proce...

Страница 10: ...g of the button 3 INSTALLATION INSTRUCTIONS Place the D64RPBH13 in a clean dry enclosure Try to keep the exposure to mechanical shock and vibration to a minimum The internal electronics have been enca...

Страница 11: ...screw clamp terminals rated 10 Amps 300 Volts Terminals will accept 26 12 AWG solid or stranded conductors The terminals are pull apart They have two 12 AWG screw clamps per pole with 90 and 180 orien...

Страница 12: ...r Toroidal C311CT9 A2 2 56 65 mm inside diameter Toroidal C311CT28 A2 1 1 28 mm inside diameter Toroidal with wire leads Zero Sequence Current Transformers with 10 000 1 ratio C311CT11 2 56 65mm insid...

Страница 13: ...ary contact Push button 3 A 10 V ac Causes an external CT Open Circuit trip by opening up the connection to the CT Local Reset Toggle Operated Circuit Breaker Reset mode Manual Ground Fault Circuit Gr...

Страница 14: ...ipping Weight 2 43 lbs 1 10 kg Applicable Standards EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environm...

Страница 15: ...Part 4 11 Voltage dips drops variations immunity EN 60947 5 1 Low voltage switchgear and controlgear Part 5 1 Control circuit devices and switching elements Electromechanical control circuit devices...

Страница 16: ...NG EQUIPMENT RELAY CLASS 1 CONTACT RATING 3A 250 VAC CT 1 CBCT SEE MANUAL FOR SET UP AND TEST INSTRUCTIONS PROD BATCH Nr P23509xxx MADE IN HOLLAND REMOTE TEST D64RPBH13 SER B1 L EN60947 5 1 EN61000 4...

Страница 17: ...74 Mounting Hole Dia 0 158 4 4 01 2 83 DOOR CUTOUT THROUGH THE DOOR MOUNTING 125 15 100 105 100 16 6 95 102 72 FIGURE 2 DIMENSIONS AND WEIGHTS OPEN WEIGHT 1 88 LBS 85KG PACKAGED WEIGHT 2 43 LBS 1 10...

Страница 18: ...ROL POWER ON NORMAL NORMAL 5 LOSS OF CONTROL POWER NORMAL TOGGLE TRIPS 6 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING NORMAL Time Delay TRIPPED Time Delay Time Delay NORMAL Time Delay TRIPPED Tim...

Страница 19: ...ion is made for external testing if required Refer to Figure 1 Select a momentary contact single pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac Connect as shown in Figure 1 When...

Отзывы: