manualshive.com logo in svg
background image

 

 

 

 

 

PUB 50413 

 

D64RPBH13 SERIES B1 GROUND FAULT RELAY 

 

Revision 2 
September, 2009 

Page 9 

 

 

Two .25 s flashes every few seconds means that the ground fault current exceeded 
the Trip Inhibit Level but the upstream device failed to trip during 1.2 s. The 
D64RPBH13 then tripped as a last resort. The contactor should be replaced since its 
contacts may well be damaged. This trip is labelled Inhibit Backup. 

 

Four 0.25 s flashes every few seconds means that the connection of the external CT is 
open circuited. Note that the trip is latched until reset; therefore intermittent failures will 
be captured, overcoming the impression that the D64RPBH3 tripped without cause. 
This trip is labelled CT Open Circuit. 

 

Five 0.25 s flashes every few seconds means that control voltage was lost while the 
D64RPBH13 was in the Failsafe operating mode. The RESET pushbutton must be 
pressed before restoring control voltage to activate this indication.    

 

Continuous 0.25 s flashes indicate an extra ‘trip failed’ alarm state on top of one of the 
possible trips described above. Following the operation of the output circuit breaker, 
measured ground fault current remained at a high level. When the local reset button is 
first pressed, the trip is not reset, but the ‘trip failed’ alarm state is. As a result the red 
LED will now show the original cause of trip. This alarm is labelled Trip Failed. 

 

Please note that the red LED is a convenient indicator only. It does not affect the operation of the output 
circuit breaker. After a fault is cleared, the user may or may not decide to reset the LED. A subsequent 
fault will cause the indication to be updated in either case. 

 
2.5 

G/F TEST - RESET

 

 

2.5.1 

G/F TEST INTERNAL

 

 

Double-clicking the built-in RESET – TEST pushbutton invokes a test which switches an AC voltage 
onto the processor’s CT sensor input. The voltage is scaled to simulate a Ground fault current of 1.5 
times the G/F trip level set point. The output circuit breaker will trip on G/F after the set delay (plus 0.4 s) 
and the AC test voltage will be switched off. The red LED will turn on solid. This proves that the internal 
electronics and output circuit breaker are functioning. Optionally, pressing the reset button again will 
reset the red LED enabling the green RUN LED. Reclose the circuit breaker (Normal position). No 
external power supply is required. 

 
2.5.2 

G/F TEST EXTERNAL

 

 

Provision is made for external testing if required. Refer to Figure 1. Select a momentary contact single 
pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac. Connect as shown in Figure 1. 
When pressed the circuit to the external CT is opened. This results in a trip and the red LED will flash 
four 0.25 s flashes (CT Open Circuit). This proves that the current transformer is connected and the 
windings are okay, the CT monitor's detection circuit is operating, and the internal electronics and output 
circuit breaker are functioning. 

 

A “Test Record Form” is included in this instruction manual. This form provides spaces to record the 
date the test was performed and the results. Those in charge of the building’s electrical installation 
should retain the form in order to be available to the authority having jurisdiction. 

 

2.5.3 

RESET

 

 

The built-in RESET – TEST pushbutton is used to optionally reset the red LAST TRIP LED in the 
D64RPBH13.  

 
 

The external pushbutton cannot be used to reset the red LAST TRIP LED.  

Содержание Cutler-Hammer D64 Series

Страница 1: ...40 45 50 55 60 10A 10A 10A 10A 10A 20A 20A 20A 20A 20A 20A 50A 50A 50A 50A 50A 50A 50A 100A 100A 100A 100A 100A 100A 100A RL 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400 450 500 550 600 700...

Страница 2: ...5 G F TEST RESET 9 2 5 1 G F TEST INTERNAL 9 2 5 2 G F TEST EXTERNAL 9 2 5 3 RESET 9 2 6 MEMORY AFTER LOSS OF CONTROL VOLTAGE 10 3 INSTALLATION INSTRUCTIONS 10 3 1 MOUNTING 10 3 1 1 THROUGH THE DOOR...

Страница 3: ...current exceeds the inhibit level the output circuit breaker trip will be inhibited until the ground fault current drops below the inhibit level A voltage operated circuit breaker with an external to...

Страница 4: ...are in the tripped state Terminals 11 14 open Terminals 11 12 closed Manual Reset The toggle of the circuit breaker must be placed in the Normal position to reset the contacts to the normal state aft...

Страница 5: ...ero sequence current transformers with a turns ratio of 500 1 With Inhibit Disabled under the same conditions the output circuit breaker will trip after the preset trip delay time The INHIBIT function...

Страница 6: ...o provide the desired delay before the output relay will trip when the ground fault TRIP LEVEL setting is reached or exceeded The setting should be selected to co ordinate with other ground fault devi...

Страница 7: ...ode DIPSWITCH SETTINGS TRIP INHIBIT MODE 11 L LEFT R RIGHT L DISABLED R ENABLED Factory Setting DIPSWITCH SETTINGS LEVELS WHEN USING C311CTs WITH 500 1 TURNS RATIO LEVELS WHEN USING C311CTs WITH 10 00...

Страница 8: ...being stored in non volatile memory remain valid The proper procedure to change settings is as follows 1 The dipswitches are placed in the new positions ignoring the blinking LEDs 2 Within 15 seconds...

Страница 9: ...use the indication to be updated in either case 2 5 G F TEST RESET 2 5 1 G F TEST INTERNAL Double clicking the built in RESET TEST pushbutton invokes a test which switches an AC voltage onto the proce...

Страница 10: ...g of the button 3 INSTALLATION INSTRUCTIONS Place the D64RPBH13 in a clean dry enclosure Try to keep the exposure to mechanical shock and vibration to a minimum The internal electronics have been enca...

Страница 11: ...screw clamp terminals rated 10 Amps 300 Volts Terminals will accept 26 12 AWG solid or stranded conductors The terminals are pull apart They have two 12 AWG screw clamps per pole with 90 and 180 orien...

Страница 12: ...r Toroidal C311CT9 A2 2 56 65 mm inside diameter Toroidal C311CT28 A2 1 1 28 mm inside diameter Toroidal with wire leads Zero Sequence Current Transformers with 10 000 1 ratio C311CT11 2 56 65mm insid...

Страница 13: ...ary contact Push button 3 A 10 V ac Causes an external CT Open Circuit trip by opening up the connection to the CT Local Reset Toggle Operated Circuit Breaker Reset mode Manual Ground Fault Circuit Gr...

Страница 14: ...ipping Weight 2 43 lbs 1 10 kg Applicable Standards EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environm...

Страница 15: ...Part 4 11 Voltage dips drops variations immunity EN 60947 5 1 Low voltage switchgear and controlgear Part 5 1 Control circuit devices and switching elements Electromechanical control circuit devices...

Страница 16: ...NG EQUIPMENT RELAY CLASS 1 CONTACT RATING 3A 250 VAC CT 1 CBCT SEE MANUAL FOR SET UP AND TEST INSTRUCTIONS PROD BATCH Nr P23509xxx MADE IN HOLLAND REMOTE TEST D64RPBH13 SER B1 L EN60947 5 1 EN61000 4...

Страница 17: ...74 Mounting Hole Dia 0 158 4 4 01 2 83 DOOR CUTOUT THROUGH THE DOOR MOUNTING 125 15 100 105 100 16 6 95 102 72 FIGURE 2 DIMENSIONS AND WEIGHTS OPEN WEIGHT 1 88 LBS 85KG PACKAGED WEIGHT 2 43 LBS 1 10...

Страница 18: ...ROL POWER ON NORMAL NORMAL 5 LOSS OF CONTROL POWER NORMAL TOGGLE TRIPS 6 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING NORMAL Time Delay TRIPPED Time Delay Time Delay NORMAL Time Delay TRIPPED Tim...

Страница 19: ...ion is made for external testing if required Refer to Figure 1 Select a momentary contact single pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac Connect as shown in Figure 1 When...

Отзывы: