manualshive.com logo in svg
background image

 

 

 

 

 

PUB 50413 

 

D64RPBH13 SERIES B1 GROUND FAULT RELAY 

 

Revision 2 
September, 2009 

Page 10 

 

2.6 

MEMORY AFTER LOSS OF CONTROL VOLTAGE 

When control voltage is removed from the D64RPBH13, the LAST TRIP registration will be memorized 
(for at least one week). Pressing the Reset pushbutton before restoring control voltage will light either 
the green LED or the red LED, green indicating no trip was registered and red indicating the opposite. 
The green LED will light continuously, whereas the red LED will give a sequence of short flashes as 
described in section 2.4 indicating the cause of trip. Please note that if the D64RPBH13 is operated in 
the Failsafe mode (see section 2.2.4), and there was no trip when control voltage disappeared, the 
system will still activate the trip register and trip the output circuit breaker at the very moment of losing 
voltage. If this is what happened, the red LED will show five consecutive short flashes, meaning ‘relay 
was merely activated because control voltage was lost while operating in Failsafe mode’.  
 
The LAST TRIP registration is written to non volatile memory at the moment the D64RPBH13 powers 
down. This way the trip code is accessible -by pressing the RESET button- even without control voltage 
present, which is particularly helpful when the tripping of the relay also causes control voltage to 
disappear. However, there is a very limited amount of backup power stored internally to support this, so 
the number of red flashes must be verified at the very moment when the button is being pressed. 
 
The backup power will hold for days as long as it is not exhausted by the pressing of the button. 
 

3. 

INSTALLATION INSTRUCTIONS 

 

Place the D64RPBH13 in a clean dry enclosure. Try to keep the exposure to mechanical shock and 
vibration to a minimum. The internal electronics have been encapsulated in epoxy to improve the 
performance in high vibration environments.  

 
 

Locate the relay close to the isolating device (circuit breaker or contactor) which is protecting the circuit 
being monitored. 

 
 

Provide maximum clearance between both the D64RPBH13 and the C311CT and any strong magnetic 
flux producing devices such as power transformers, autotransformers, control transformers, reactors, 
and high power conductors and buswork.  

3.1 

MOUNTING

 

 

Refer to Figure 2 for mounting dimensions of the D64RPBH13 relay. It is designed for through-the-door 
or rear panel mounting. 

3.1.1 

THROUGH-THE-DOOR

 

 

Four 4 mm (5/32") holes in the flanged cover of the relay permit bolting to the door using suitable 
hardware. 

 
 

A 102 mm high (4.0") x 72 mm wide (2.85") cut-out is required in the door. 

 

 

Remove the pull-apart terminal block from the relay to permit the relay to be inserted through the cut-
out. From the front of the door, insert the relay through the cut-out. Mount the relay cover to the front of 
the door using the customer supplied mounting hardware (four bolts, washers and nuts). 

 

3.1.2 

REAR PANEL

 

 

The relay may be mounted with either mounting screws or 35 mm DIN rail.  

 
 

Two #8-32 x 3/4" (M4 x 20) mounting screws are required for screw mounting. 

 
 

For DIN rail mounting, the rail should be bolted to a flat surface. Install the DIN rail vertically. Allow at 
least 1" (25.4 mm) of rail to extend beyond each end of the relay. Install a stop block on the DIN rail 1" 
(25.4 mm) from the bottom to keep the D64RPBH13 in position. Secure the relay to the DIN rail 
ensuring the white release latch at the left side of the relay engages the rail. 

Содержание Cutler-Hammer D64 Series

Страница 1: ...40 45 50 55 60 10A 10A 10A 10A 10A 20A 20A 20A 20A 20A 20A 50A 50A 50A 50A 50A 50A 50A 100A 100A 100A 100A 100A 100A 100A RL 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400 450 500 550 600 700...

Страница 2: ...5 G F TEST RESET 9 2 5 1 G F TEST INTERNAL 9 2 5 2 G F TEST EXTERNAL 9 2 5 3 RESET 9 2 6 MEMORY AFTER LOSS OF CONTROL VOLTAGE 10 3 INSTALLATION INSTRUCTIONS 10 3 1 MOUNTING 10 3 1 1 THROUGH THE DOOR...

Страница 3: ...current exceeds the inhibit level the output circuit breaker trip will be inhibited until the ground fault current drops below the inhibit level A voltage operated circuit breaker with an external to...

Страница 4: ...are in the tripped state Terminals 11 14 open Terminals 11 12 closed Manual Reset The toggle of the circuit breaker must be placed in the Normal position to reset the contacts to the normal state aft...

Страница 5: ...ero sequence current transformers with a turns ratio of 500 1 With Inhibit Disabled under the same conditions the output circuit breaker will trip after the preset trip delay time The INHIBIT function...

Страница 6: ...o provide the desired delay before the output relay will trip when the ground fault TRIP LEVEL setting is reached or exceeded The setting should be selected to co ordinate with other ground fault devi...

Страница 7: ...ode DIPSWITCH SETTINGS TRIP INHIBIT MODE 11 L LEFT R RIGHT L DISABLED R ENABLED Factory Setting DIPSWITCH SETTINGS LEVELS WHEN USING C311CTs WITH 500 1 TURNS RATIO LEVELS WHEN USING C311CTs WITH 10 00...

Страница 8: ...being stored in non volatile memory remain valid The proper procedure to change settings is as follows 1 The dipswitches are placed in the new positions ignoring the blinking LEDs 2 Within 15 seconds...

Страница 9: ...use the indication to be updated in either case 2 5 G F TEST RESET 2 5 1 G F TEST INTERNAL Double clicking the built in RESET TEST pushbutton invokes a test which switches an AC voltage onto the proce...

Страница 10: ...g of the button 3 INSTALLATION INSTRUCTIONS Place the D64RPBH13 in a clean dry enclosure Try to keep the exposure to mechanical shock and vibration to a minimum The internal electronics have been enca...

Страница 11: ...screw clamp terminals rated 10 Amps 300 Volts Terminals will accept 26 12 AWG solid or stranded conductors The terminals are pull apart They have two 12 AWG screw clamps per pole with 90 and 180 orien...

Страница 12: ...r Toroidal C311CT9 A2 2 56 65 mm inside diameter Toroidal C311CT28 A2 1 1 28 mm inside diameter Toroidal with wire leads Zero Sequence Current Transformers with 10 000 1 ratio C311CT11 2 56 65mm insid...

Страница 13: ...ary contact Push button 3 A 10 V ac Causes an external CT Open Circuit trip by opening up the connection to the CT Local Reset Toggle Operated Circuit Breaker Reset mode Manual Ground Fault Circuit Gr...

Страница 14: ...ipping Weight 2 43 lbs 1 10 kg Applicable Standards EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environm...

Страница 15: ...Part 4 11 Voltage dips drops variations immunity EN 60947 5 1 Low voltage switchgear and controlgear Part 5 1 Control circuit devices and switching elements Electromechanical control circuit devices...

Страница 16: ...NG EQUIPMENT RELAY CLASS 1 CONTACT RATING 3A 250 VAC CT 1 CBCT SEE MANUAL FOR SET UP AND TEST INSTRUCTIONS PROD BATCH Nr P23509xxx MADE IN HOLLAND REMOTE TEST D64RPBH13 SER B1 L EN60947 5 1 EN61000 4...

Страница 17: ...74 Mounting Hole Dia 0 158 4 4 01 2 83 DOOR CUTOUT THROUGH THE DOOR MOUNTING 125 15 100 105 100 16 6 95 102 72 FIGURE 2 DIMENSIONS AND WEIGHTS OPEN WEIGHT 1 88 LBS 85KG PACKAGED WEIGHT 2 43 LBS 1 10...

Страница 18: ...ROL POWER ON NORMAL NORMAL 5 LOSS OF CONTROL POWER NORMAL TOGGLE TRIPS 6 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING NORMAL Time Delay TRIPPED Time Delay Time Delay NORMAL Time Delay TRIPPED Tim...

Страница 19: ...ion is made for external testing if required Refer to Figure 1 Select a momentary contact single pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac Connect as shown in Figure 1 When...

Отзывы: