background image

1

Operating Instructions

Safety Relay ESM-BT4..

Correct use

ESM-BT4.. is an emergency stop safety relay com-

bination that combines non-time-delayed (u) and 

time-delayed (v) contacts in a very compact housing. 

This permits dangerous components of a system to 

be switched off quickly and safely in an emergency 

situation. At the same time, other safety circuits 

can continue to be supplied with power for up to 

30 seconds to allow a tool to be moved to its idle 

position or to brake overtraveling parts, for example.
Before the device is used, a risk assessment must 

be performed on the machine, e.g. according to the 

following standards:

 

f

EN ISO 13849-1

 

f

EN ISO 12100

 

f

IEC 62061.

Correct use includes observing the relevant require-

ments for installation and operation, particularly 

based on the following standards:

 

f

EN ISO 13849-1

 

f

EN 60204-1

 

f

IEC 62061.

Important!

 

f

The user is responsible for the integration of 

the device in a safe overall system. For this 

purpose, the overall system must be validated, 

e.g. according to EN ISO 13849-2.

 

f

The device user must assess and document 

remaining risks.

 

f

If a data sheet is included with the product, the 

information on the data sheet applies.

Safety precautions

 WARNING

 

f

Installation and setup of the device must be 

performed only by authorized personnel.

 

f

Observe the country-specific regulations when 

installing the device.

 

f

The electrical connection of the device is only 

allowed to be made with the device isolated.

 

f

The wiring of the device must comply with the 

instructions in these operating instructions, 

otherwise there is a risk that the safety function 

will be lost.

 

f

It is not allowed to open the device, tamper with 

the device or bypass the safety devices.

 

f

All relevant safety regulations and standards are 

to be observed.

 

f

The overall concept of the control system in 

which the device is incorporated must be vali-

dated by the user.

 

f

Failure to observe the safety regulations can re-

sult in death, severe injuries and serious damage.

 

f

Note down the version of the device (see type la-

bel 

Vx.x.x

) and check it each time prior to setup. 

If the version changes, the use of the device in 

the overall application must be validated again.

Features

 

f

4 safe, redundant relay outputs. Depending on 

variant:
-  3 non-time-delayed contacts, 1 time-delayed 

contact

-  2 non-time-delayed contacts, 2 time-delayed 

contacts 

-  1 non-time-delayed contact, 3 time-delayed 

contacts

 

f

Continuously adjustable delay time (1  …  30  s) 

or fixed delay time (ESM-BT4..-20S (2  s); 

ESM-BT4..-50S (5 s))

 

f

Connection of:
- Emergency stop buttons
- Safety switches
- Non-contact safety switches
- Safety components with OSSD outputs

 

f

Single- and dual-channel operation possible

 

f

Feedback loop for monitoring downstream contac-

tors or expansion modules

 

f

Cyclical monitoring of the output contacts

 

f

Indication of the switching state via LED

 

f

2 starting behaviors possible:
- Monitored manual start
- Automatic start

 

f

Short circuit and ground fault monitoring

 

f

Use up to PL e, SILCL 3, category 4

Function

The moving parts of a machine or system can be 

quickly and safely stopped in case of danger with the 

non-time-delayed contacts of the ESM-BT4... Safety 

contacts with time-delay switch-off are also integrat-

ed into the ESM-BT4... They are used whenever it is 

safer to keep supplying power to parts of a machine 

after the emergency stop button is actuated.
It is ensured that a single fault or malfunction does 

not lead to a loss of the safety function and that 

every fault is detected by cyclical self-monitoring 

no later than when the system is switched off and 

switched on again.
The time-delayed contacts switch on at the same 

time as the non-time-delayed contacts, but they are 

switched off again only after the time set on the 

potentiometer elapses (1 … 30 s) or after a fixed 

delay time (ESM-BT4..-20S; ESM-BT4..-50S) when 

the emergency stop button is operated.
The power supply must be present during the time 

sequence.

ESM-BT401 (1 non-time-delayed/3 time-delayed)

ESM-BT411 (2 non-time-delayed/2 time-delayed);

ESM-BT421 (3 non-time-delayed/1 time-delayed)

Fig. 1:  Block diagrams ESM-BT4..

Mounting

As per EN 60204-1, the device is intended for in-

stallation in control cabinets with a minimum degree 

of protection of IP54. It is mounted on a 35 mm 

mounting rail according to DIN EN 60715 TH35.

Fig. 2:  Mounting/removing

Electrical connection

 

f

A safety transformer according to EN 61558-2-6 or 

a power supply unit with electrical isolation from 

the mains must be connected.

 

f

External fusing of the safety contacts must be 

provided.

 

f

A maximum length of the control lines of 1,000 m 

with a conductor cross-section of 0.75 mm² must 

not be exceeded.

 

f

The conductor cross-section must not exceed 

2.5 mm².

 

f

If the device does not function after setup, it must 

be returned to the manufacturer unopened. Open-

ing the device will void the warranty.

A1

Power supply

A2

Power supply

S11

DC 24 V control voltage

S10

Control line

S21

Start control line

S13

Control line

S14

Control line

S12

Control line

13-14

Safety contact 1 (u)

23-24 /

27-28

Safety contact 2 (u / v)

33-34 /

37-38

Safety contact 3 (u / v)

47-48

Safety contact 4 (v)

Fig. 3:   Connections 

(u = non-time-delayed, v = time-delayed)

Setup procedure

Notice

The items listed under 

Electrical connection

 must 

be observed during setup.

1. Wiring emergency stop circuit:

Wire the emergency stop circuit according to the 

required Performance Level determined (see Fig. 

5 to Fig. 9).

2. Wiring start circuit:

Wire the start circuit according to Fig. 10 or Fig. 11 

to set the starting behavior.

Attention: 

If 

Automatic start

 is set, bear in mind that 

the safety contacts will switch immediately after the 

power supply is connected. If 

Monitored manual start

 

is set, the start button must be opened after wiring.

3. Wiring feedback loop:

If your application provides for external contactors 

or expansion modules, connect them to the device 

according to Fig. 12 or Fig. 13.

Summary of Contents for ESM-BT4 Series

Page 1: ... via LED f 2 starting behaviors possible Monitored manual start Automatic start f Short circuit and ground fault monitoring f Use up to PL e SILCL 3 category 4 Function The moving parts of a machine or system can be quickly and safely stopped in case of danger with the non time delayed contacts of the ESM BT4 Safety contacts with time delay switch off are also integrat ed into the ESM BT4 They are...

Page 2: ...ncy stop circuit is closed f Check whether the start button with manual start is closed f Check the operating voltage at A1 and A2 f Is the feedback loop closed Device cannot be switched on again after an emergency stop f Check whether the emergency stop circuit was closed again f Was the start button opened before closing of the emergency stop circuit with manual start f Is the feedback loop clos...

Page 3: ...Contact material AgSnO2 Mech contact life Approx 1 x 107 Test voltage 2 5 kV control voltage contacts Rated impulse withstand voltage leakage paths air gaps 4 kV DIN VDE 0110 1 Rated insulation voltage 250 V Degree of protection IP20 Temperature range 15 C to 40 C 1 Degree of contamination 2 DIN VDE 0110 1 Overvoltage category 3 DIN VDE 0110 1 Weight Approx 250 g Mounting Mounting rail according t...

Page 4: ... Wire the start circuit in accordance with the applica tion according to Bild 10 or Bild 11 Fig 8 Dual channel sliding guard monitoring with short circuit and ground fault monitoring category 4 up to PL e Fig 9 Dual channel emergency stop circuit with pnp semiconductor outputs OSSD outputs with short circuit detection category 4 up to PL e Starting behavior Attention Safety contacts switch immedia...

Reviews: