PUB 50413 

 

D64RPBH13 SERIES B1 GROUND FAULT RELAY 

 

Revision 2 
September, 2009 

Page 5 

 

 

  Trip Free: 

 

The output circuit breaker is 'trip free', meaning that its contact cannot be held closed against a 

fault by manually keeping the toggle in the NORMAL position. Note however that this is only 
true when control voltage is present on terminals L+ and N-. 

 
 

  

Trip Inhibit:

 

 

 

Contactors are not designed to interrupt high fault currents. Under these conditions the 
upstream short circuit protective devices, fuses or circuit breaker, should interrupt the fault.  

 

 

Trip INHIBIT function can be Enabled or Disabled by means of DIPswitch no. 11. The inhibit 
level is related to the ground fault trip level over a range of 200 Amps to 2000 amps when 
using the special Eaton’s Cutler-Hammer C311CT zero sequence current transformer with a 
turns ratio of 10000:1. With Inhibit Enabled, if the ground fault current exceeds the inhibit level 
the output circuit breaker will be inhibited until the ground fault current drops below the inhibit 
level. However, should the current fail to drop within 1.2 s, then, as a last resort, the unit will trip 
showing the ‘Inhibit Backup Trip’ code on its red LED (2 flashes). It is advisable to replace the 
contactor after this event since it was used to break a current possibly well outside its rating. 

 
 

 

The inhibit level is related to the ground fault trip level over a range of 10 Amps to 100 amps, 
when using the standard family of C311CT zero sequence current transformers with a turns 
ratio of 500:1. 

 
 

 

With Inhibit Disabled under the same conditions, the output circuit breaker will trip after the 
preset trip delay time. 

 
 

 

The INHIBIT function is useful when the D64RPBH13 is being used to trip a contactor or motor 
starter on a solidly grounded system. In this application, there is no defined limit to the 
magnitude of ground fault current should a bolted ground fault occur. By inhibiting the trip it 
allows the upstream protective device to clear the fault.   

 

 

MEMORY AFTER LOSS OF CONTROL VOLTAGE 

When control voltage is removed from the D64RPBH13, the LAST TRIP registration will be 
memorized (for at least one week). Pressing the Reset pushbutton before restoring control 
voltage will light either the green LED or the red LED, green indicating no trip was registered 
and red indicating the opposite. The green LED will light continuously, whereas the red LED will 
give a sequence of short flashes as described in section 2.4 indicating the cause of trip.  
 

2.2 

DIPSWITCH SETTINGS

 

 
 

Refer to the figure on the front page of this manual. There is one 12 - position array of DIPswitches on 
the front of the D64RPBH13. The factory setting of all DIPswitches is LEFT (L). 

 
 

Position 1 - 4: 

 

 

 

 

 

These four DIPswitches (1, 2, 3, & 4) are assigned to Ground Fault TRIP DELAY settings. 

 
 

Position 5 - 8: 

 

 

These five DIPswitches (5, 6, 7, 8, & 9) are assigned to Ground Fault TRIP LEVEL 
and TRIP INHIBIT LEVEL settings.  

 
 

Position 10: 

 

 

This DIPswitch is reserved for use in the D64RPBH15 relay 

 
 

Position 11: 

 

 

This DIPswitch is assigned to TRIP INHIBIT MODE. 

 
 

Position 12: 

 

 

This DIPswitch is assigned to Output Circuit Breaker OPERATING MODE. 

Содержание Cutler-Hammer D64 Series

Страница 1: ...40 45 50 55 60 10A 10A 10A 10A 10A 20A 20A 20A 20A 20A 20A 50A 50A 50A 50A 50A 50A 50A 100A 100A 100A 100A 100A 100A 100A RL 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400 450 500 550 600 700...

Страница 2: ...5 G F TEST RESET 9 2 5 1 G F TEST INTERNAL 9 2 5 2 G F TEST EXTERNAL 9 2 5 3 RESET 9 2 6 MEMORY AFTER LOSS OF CONTROL VOLTAGE 10 3 INSTALLATION INSTRUCTIONS 10 3 1 MOUNTING 10 3 1 1 THROUGH THE DOOR...

Страница 3: ...current exceeds the inhibit level the output circuit breaker trip will be inhibited until the ground fault current drops below the inhibit level A voltage operated circuit breaker with an external to...

Страница 4: ...are in the tripped state Terminals 11 14 open Terminals 11 12 closed Manual Reset The toggle of the circuit breaker must be placed in the Normal position to reset the contacts to the normal state aft...

Страница 5: ...ero sequence current transformers with a turns ratio of 500 1 With Inhibit Disabled under the same conditions the output circuit breaker will trip after the preset trip delay time The INHIBIT function...

Страница 6: ...o provide the desired delay before the output relay will trip when the ground fault TRIP LEVEL setting is reached or exceeded The setting should be selected to co ordinate with other ground fault devi...

Страница 7: ...ode DIPSWITCH SETTINGS TRIP INHIBIT MODE 11 L LEFT R RIGHT L DISABLED R ENABLED Factory Setting DIPSWITCH SETTINGS LEVELS WHEN USING C311CTs WITH 500 1 TURNS RATIO LEVELS WHEN USING C311CTs WITH 10 00...

Страница 8: ...being stored in non volatile memory remain valid The proper procedure to change settings is as follows 1 The dipswitches are placed in the new positions ignoring the blinking LEDs 2 Within 15 seconds...

Страница 9: ...use the indication to be updated in either case 2 5 G F TEST RESET 2 5 1 G F TEST INTERNAL Double clicking the built in RESET TEST pushbutton invokes a test which switches an AC voltage onto the proce...

Страница 10: ...g of the button 3 INSTALLATION INSTRUCTIONS Place the D64RPBH13 in a clean dry enclosure Try to keep the exposure to mechanical shock and vibration to a minimum The internal electronics have been enca...

Страница 11: ...screw clamp terminals rated 10 Amps 300 Volts Terminals will accept 26 12 AWG solid or stranded conductors The terminals are pull apart They have two 12 AWG screw clamps per pole with 90 and 180 orien...

Страница 12: ...r Toroidal C311CT9 A2 2 56 65 mm inside diameter Toroidal C311CT28 A2 1 1 28 mm inside diameter Toroidal with wire leads Zero Sequence Current Transformers with 10 000 1 ratio C311CT11 2 56 65mm insid...

Страница 13: ...ary contact Push button 3 A 10 V ac Causes an external CT Open Circuit trip by opening up the connection to the CT Local Reset Toggle Operated Circuit Breaker Reset mode Manual Ground Fault Circuit Gr...

Страница 14: ...ipping Weight 2 43 lbs 1 10 kg Applicable Standards EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environm...

Страница 15: ...Part 4 11 Voltage dips drops variations immunity EN 60947 5 1 Low voltage switchgear and controlgear Part 5 1 Control circuit devices and switching elements Electromechanical control circuit devices...

Страница 16: ...NG EQUIPMENT RELAY CLASS 1 CONTACT RATING 3A 250 VAC CT 1 CBCT SEE MANUAL FOR SET UP AND TEST INSTRUCTIONS PROD BATCH Nr P23509xxx MADE IN HOLLAND REMOTE TEST D64RPBH13 SER B1 L EN60947 5 1 EN61000 4...

Страница 17: ...74 Mounting Hole Dia 0 158 4 4 01 2 83 DOOR CUTOUT THROUGH THE DOOR MOUNTING 125 15 100 105 100 16 6 95 102 72 FIGURE 2 DIMENSIONS AND WEIGHTS OPEN WEIGHT 1 88 LBS 85KG PACKAGED WEIGHT 2 43 LBS 1 10...

Страница 18: ...ROL POWER ON NORMAL NORMAL 5 LOSS OF CONTROL POWER NORMAL TOGGLE TRIPS 6 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING NORMAL Time Delay TRIPPED Time Delay Time Delay NORMAL Time Delay TRIPPED Tim...

Страница 19: ...ion is made for external testing if required Refer to Figure 1 Select a momentary contact single pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac Connect as shown in Figure 1 When...

Отзывы: