D64RPBH13 SERIES B1 GROUND FAULT RELAY 

 

Revision 2 
September, 2009 

Page 7 

 

 

Table 2: Ground Fault Trip Level 

 
 

As indicated in the General Description, it is recommended that the ground fault TRIP LEVEL setting be 
kept as close to the charging current as possible. This will provide maximum safety for operating 
personnel and equipment protection. On resistance grounded systems, the TRIP LEVEL setting should 
be set lower than 20% of the Neutral Grounding Resistor let-through current.  

 
 

If the measured ground fault current exceeds the TRIP LEVEL setting, the output circuit breaker will trip 
after the pre-selected TRIP DELAY. 

 

2.2.3 

TRIP INHIBIT MODE

 

 

TRIP INHIBIT is described under the glossary of terms. The setting of DIPswitch 11 determines if TRIP 
INHIBIT is disabled or enabled. This is shown in Table 3.  

 
Table 3: Trip Inhibit Mode 

 

DIPSWITCH 

SETTINGS 

TRIP 

INHIBIT 

MODE 

11 

L=LEFT 

R=RIGHT 

* DISABLED 

ENABLED 

* Factory Setting 

DIPSWITCH 

SETTINGS 

LEVELS WHEN USING C311CTs  

WITH 500:1 TURNS RATIO 

LEVELS WHEN USING C311CTs  

WITH 10,000:1 TURNS RATIO 

 7 

  8 

 9 

TRIP LEVEL 

IN AMPS 

INHIBIT LEVEL 

IN AMPS 

(When INHIBIT is 

Enabled) 

TRIP LEVEL 

IN AMPS 

INHIBIT LEVEL 

IN AMPS 

(When INHIBIT is 

Enabled) 

L=LEFT  

R=RIGHT 

* 2.5 

10 

*

 50 

200 

10 

  60 

200 

3.5 

10 

  70 

200 

10 

  80 

200 

4.5 

10 

  90 

200 

20 

100 

400 

20 

120 

400 

20 

140 

400 

20 

160 

400 

20 

180 

400 

10 

20 

200 

400 

12.5 

50 

250 

1000 

15 

50 

300 

1000 

17.5 

50 

350 

1000 

20 

50 

400 

1000 

22.5 

50 

450 

1000 

25 

50 

500 

1000 

27.5 

50 

550 

1000 

30 

100 

600 

2000 

35 

100 

700 

2000 

40 

100 

800 

2000 

45 

100 

900 

2000 

50 

100 

1000 

2000 

55 

100 

1100 

2000 

60 

100 

1200 

2000 

 

 

 

 

 

* Factory 

Setting

 

 

* Factory 

Setting 

 

Содержание Cutler-Hammer D64 Series

Страница 1: ...40 45 50 55 60 10A 10A 10A 10A 10A 20A 20A 20A 20A 20A 20A 50A 50A 50A 50A 50A 50A 50A 100A 100A 100A 100A 100A 100A 100A RL 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400 450 500 550 600 700...

Страница 2: ...5 G F TEST RESET 9 2 5 1 G F TEST INTERNAL 9 2 5 2 G F TEST EXTERNAL 9 2 5 3 RESET 9 2 6 MEMORY AFTER LOSS OF CONTROL VOLTAGE 10 3 INSTALLATION INSTRUCTIONS 10 3 1 MOUNTING 10 3 1 1 THROUGH THE DOOR...

Страница 3: ...current exceeds the inhibit level the output circuit breaker trip will be inhibited until the ground fault current drops below the inhibit level A voltage operated circuit breaker with an external to...

Страница 4: ...are in the tripped state Terminals 11 14 open Terminals 11 12 closed Manual Reset The toggle of the circuit breaker must be placed in the Normal position to reset the contacts to the normal state aft...

Страница 5: ...ero sequence current transformers with a turns ratio of 500 1 With Inhibit Disabled under the same conditions the output circuit breaker will trip after the preset trip delay time The INHIBIT function...

Страница 6: ...o provide the desired delay before the output relay will trip when the ground fault TRIP LEVEL setting is reached or exceeded The setting should be selected to co ordinate with other ground fault devi...

Страница 7: ...ode DIPSWITCH SETTINGS TRIP INHIBIT MODE 11 L LEFT R RIGHT L DISABLED R ENABLED Factory Setting DIPSWITCH SETTINGS LEVELS WHEN USING C311CTs WITH 500 1 TURNS RATIO LEVELS WHEN USING C311CTs WITH 10 00...

Страница 8: ...being stored in non volatile memory remain valid The proper procedure to change settings is as follows 1 The dipswitches are placed in the new positions ignoring the blinking LEDs 2 Within 15 seconds...

Страница 9: ...use the indication to be updated in either case 2 5 G F TEST RESET 2 5 1 G F TEST INTERNAL Double clicking the built in RESET TEST pushbutton invokes a test which switches an AC voltage onto the proce...

Страница 10: ...g of the button 3 INSTALLATION INSTRUCTIONS Place the D64RPBH13 in a clean dry enclosure Try to keep the exposure to mechanical shock and vibration to a minimum The internal electronics have been enca...

Страница 11: ...screw clamp terminals rated 10 Amps 300 Volts Terminals will accept 26 12 AWG solid or stranded conductors The terminals are pull apart They have two 12 AWG screw clamps per pole with 90 and 180 orien...

Страница 12: ...r Toroidal C311CT9 A2 2 56 65 mm inside diameter Toroidal C311CT28 A2 1 1 28 mm inside diameter Toroidal with wire leads Zero Sequence Current Transformers with 10 000 1 ratio C311CT11 2 56 65mm insid...

Страница 13: ...ary contact Push button 3 A 10 V ac Causes an external CT Open Circuit trip by opening up the connection to the CT Local Reset Toggle Operated Circuit Breaker Reset mode Manual Ground Fault Circuit Gr...

Страница 14: ...ipping Weight 2 43 lbs 1 10 kg Applicable Standards EN 61000 6 3 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environm...

Страница 15: ...Part 4 11 Voltage dips drops variations immunity EN 60947 5 1 Low voltage switchgear and controlgear Part 5 1 Control circuit devices and switching elements Electromechanical control circuit devices...

Страница 16: ...NG EQUIPMENT RELAY CLASS 1 CONTACT RATING 3A 250 VAC CT 1 CBCT SEE MANUAL FOR SET UP AND TEST INSTRUCTIONS PROD BATCH Nr P23509xxx MADE IN HOLLAND REMOTE TEST D64RPBH13 SER B1 L EN60947 5 1 EN61000 4...

Страница 17: ...74 Mounting Hole Dia 0 158 4 4 01 2 83 DOOR CUTOUT THROUGH THE DOOR MOUNTING 125 15 100 105 100 16 6 95 102 72 FIGURE 2 DIMENSIONS AND WEIGHTS OPEN WEIGHT 1 88 LBS 85KG PACKAGED WEIGHT 2 43 LBS 1 10...

Страница 18: ...ROL POWER ON NORMAL NORMAL 5 LOSS OF CONTROL POWER NORMAL TOGGLE TRIPS 6 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING NORMAL Time Delay TRIPPED Time Delay Time Delay NORMAL Time Delay TRIPPED Tim...

Страница 19: ...ion is made for external testing if required Refer to Figure 1 Select a momentary contact single pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac Connect as shown in Figure 1 When...

Отзывы: