background image

1. APPLICATION

The conductive operating principle is suitable for liquids with a specific conductivity of over 

 

10 μS / cm. The signal processor detects the resistance between the auxiliary probe and the 

sensing probes. Conductive devices can only be used to decide whether the level of the mea

-

sured medium is at a particular level or not. The level of detection is determined by the length 

of the probe stem extending into the tank.

The level switch consists of the 

NIVOCONT KRK–512–5

 signal processor and probes select-

ed for the particular application. The part of the probe that can be screwed into the tank is 

 

NIVOCONT KS

0

 probe head carrying one or more 

KLN–2



 probe stems. If the 

inside of the tank is coated or non-conductive, an auxiliary probe has to be installed, which is 

longer than both sensing probes. If the tank’s walls are conductive, they can be used as an 

auxiliary probe.Conductive switches can control the filling and emptying of the tank or generic 

level detection.

2. TECHNICAL DATA 

2.1 GENERAL DATA

2.1.1 Switch

KRK–512–5

Probe voltage

max. 3.5 V AC

Probe current

< 0.1 mA  AC

Sensitivity

Adjustable: 5…100 kΩ 

Max. cable capacitance

800 nF (5 kΩ) 100nF (100 kΩ)

Response time

max. 400 ms

Mechanical accuracy

±5%

Delay

Adjustable: 0.5…10 s

t

1

 delay

1.5 s

Relay output

1× toggle (SPDT)

Switching voltage

250 V AC1, 24 V DC

Switching current

8 A  AC1

Switching power

2000 VA AC1, 240 W DC

Min. output power DC

500 mW

Mechanical life-span

1 × 10

7

 switchings 

Electrical life-span

1 × 10

5

 switchings 

Power supply U

n

24…240 V AC/DC (AC 50–60 Hz)

Voltage range allowed

nominal voltage –15%…+10%

Power consumption

max. 2 VA

Ambient temperature

−20…+55 °C (–4…+131 °F)

Electrical connection

max. 2.5 mm

2

 

(AWG14)

  

/ with insulation 1.5 mm

2  

(AWG16)

Electrical protection 

Class II 

Overvoltage category*

II

Pollution degree

2

Ingress protection

IP20

Mechanical connection

DIN (EN 60715) rail

Weight

72 g 

(0.16 lb)

*EN61010-1, tested with 3 kV

krk512en1906h

Thank you for choosing a NIVELCO instrument!

NIVOCONT K

KRK–512

CONDUCTIVE LEVEL SWITCH

Manufacturer:

NIVELCO Process Control Co.

H–1043 Budapest, Dugonics u. 11.

Tel.: +36-1-889-0100

  

  

Fax: +36-1-889-0200

E-mail: sales@nivelco.com  

  www.nivelco.com

USER’S MANUAL

PDF 

KRK–512–

    

NIVOCONT KS

  

  

0

KLN–2



    

Type

Code

Cable probe

K

SINGLE PROBE

PP socket

P

Carbon steel socket

S

Stainless steel socket

N

MULTIPLE PROBES

Stainless steel socket

H

Housing mat. Code

Aluminum

2

Plastic

3

Probe number

Code

1 + reference probe*

1*

2 + reference probe

2

3 + reference probe

3

4 + reference probe

4

Power supply

Code

24…240 V AC/DC

5

Code

Probe length

Code

0

0 m

0 m

0

1

1 m

 

(3.3 ft) 0.5 m (1.64 ft)

5

2

2 m (6.6 ft)

3

3 m (10 ft)

2.2 

ORDER CODES

2.4 DIMENSIONS

2.3 ACCESSORIES

 

– User’s Manual

 

– Warranty Card

 

– EU declaration of conformity

 

– Seal (2 mm [0.08"] thick) 

 

(KLINGER OILIT):

  

1× ⅜" (KSP–201, KSS–201, KSN–201)

 

1× 1½" (KSH–20

)

 

– M6 nut (standard SW): 

 

3× (KSH–202)

 

4× (KSH–203, KSH–204)

 

– M6 nut (non-st. SW) 

 

1× (KSH–204)

KSK–

201

KSP–

201

KSS–

201

KSN–

201

KSH–

KLN–

2



KLP–

201

KLP–

204

202

203

204

301

302

303

304

Number of probes

1

2+r

3+r

4+r

1+r

2+r

3+r

4+r

1

Insulation of socket ABS

PP

PFA

PP

Cable gland

Pg7

M4 nut, 

protected by a rubber cap

M20x1.5

cable diameter Ø6…12 mm (Ø0.25…0.5 inch)

Process conn.

⅜" BSP

1½" BSP

M6

Socket material

PP

A44

 

c. steel

KO35  

stainless steel (1.4571)

PP

KO35

1.4571

Housing material

Powder-coated  

cast aluminum

PBT

PP

PVDF

Medium 

 

temperature

max. +80 °C 

(+176 °F)

max. +200 °C (+391 °F)

max. +80 °C (+176 °F)

max. 

+80 °C

(+176 °F)

max. 

+130 °C

(+266 °F)

Max. pressure

3 bar 

(43.5 psi)

16 bar (232 psi)

3 bar (43.5 psi)

Ingress protection

IP20

IP65

IP67

Mass

50 g

(0.11 lb)

100 g 

(0.22 lb)

400 g (0.88 lb) 

220 g/m

(0.13 lb/ft)

r = reference probe

2.1.2 Probe sockets

Pg7

M20x1.5

⅜" BSP

Switch

KRK–512–

Cable Probe

KSK–201

Probe Socket

KSH–20

Probe Socket

KSP–201 / KSS–201 / KSN–201

Probe

KLN–2



Uninsulated base probe

M20x1.5

85

Probe Socket

KRK–512–

Separator 

KLP–204

Probe Socket

KSH–30

Separator 

KLP–201

Separator:

NIVOCONT KLP–201

 – for plastic version

NIVOCONT KLP–204

 – for aluminum version

*only plastic version

Reviews: