76
ARCON 3G
ARCON 3G MANUAL
MN026015EN October 2020 www.eaton.com
Extended system – Events & Alarms
Prefix Number Text
Description
ACK
Relay
TRIP 1
Relay
TRIP 2
Relay
TRIP 3
Relay
Trip alarm
Relay
Watchdog
LED System
LED TRIP
LED RUN
9
LED TRIP
10
IGNITION PIN
E
31
ICOM CONSTELLATION ERROR
iCOM unit missing or unexpected unit detected.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
32
ICOM COMPATIBILITY ERROR
iCOM compatibility error.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
33
IGNITION WIRE FAULT 1
Ignition port wire fault 1 error detected.
YES
-
-
-
-
OPENED
Red / 2Hz
-
OFF
-
-
E
34
IGNITION WIRE FAULT 2
Ignition port wire fault 2 error detected.
YES
-
-
-
-
OPENED
Red / 2Hz
-
OFF
-
-
E
35
IGNITION VOLTAGE ERROR 1
Ignition port voltage level 1 error.
YES
-
-
-
-
OPENED
Red / 2Hz
-
OFF
-
-
E
36
IGNITION VOLTAGE ERROR 2
Ignition port voltage level 2 error.
YES
-
-
-
-
OPENED
Red / 2Hz
-
OFF
-
-
E
37
MASTERLINK ERROR
MASTERLINK communication error.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
38
MASTER CONSTELLATION ERROR
Master missing on the MASTERLINK.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
39
MASTERLINK COMPATIBILITY ERROR
MASTERLINK compatibility error.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
40
MASTER ADDRESS CONFLICT
Address conflict detected on the MASTERLINK.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
41
MAC ADDRESS CONFLICT
MASTERLINK: MAC address conflict detected.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
42
PORT 1 LINK ESTABLISHED
MASTERLINK port 1 link established.
NO
-
-
-
-
-
-
-
-
-
-
43
PORT 2 LINK ESTABLISHED
MASTERLINK port 2 link established.
NO
-
-
-
-
-
-
-
-
-
-
44
CURRENT di/dt
di/dt limit exceeded.
NO
-
-
-
-
-
-
-
-
-
-
46
LIGHT DETECTION
Sensor detected light.
NO
-
-
-
-
-
-
-
-
-
-
E
47
FAULTY LIGHT DETECTION
Too long light detection (>10s).
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
48
OVERHEAT
Master module overheat. Temperature is too high.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
49
AUXILIARY VOLTAGE LOW
Auxiliary voltage is too low.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
50
GU: WD RESET
On chip watchdog reset happened.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
51
GU: FLASH ERROR
Access to flash memory fails.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
52
GU: PARAMETER ERROR
Parameter file missing or corrupted on the HMI.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
E
53
ALARM LIST OVERFLOW
There is no more space for alarms in the Alarm list.
YES
-
-
-
-
OPENED
Red / 2Hz
-
-
-
-
Table 3 .6: Extended system – Events & Alarm