78
ARCON 3G
ARCON 3G MANUAL
MN026015EN October 2020 www.eaton.com
Alarm Text
Trigger
Solution
E.¬¬04 Addressing error
INTERLINK
Check if all INTERLINK cables are connected properly and
the RJ45 terminator on the last module has been placed
on OUT. Restart the system and try to acknowledge the
alarm.
E.06
Flash access error
Internal hardware of master module
Restart the system and try to acknowledge the alarm.
If not possible please contact the manufacturer.
E.09
Parameterization error
INTERLINK
Check if all INTERLINK cables are connected properly,
restart the system and try to acknowledge the alarm.
Tip:
Do not disconnect any INTERLINK cable while
initialization process (SYSTEM LED blinking orange),
because it can produce this alarm
E.14
WD reset
Internal hardware of master module or a connected
module
Restart the system and try to acknowledge the alarm.
If not possible please contact the manufacturer.
E.15
ADC error
Internal hardware of master module or a connected
module
Restart the system and try to acknowledge the alarm.
If not possible please contact the manufacturer
E.16
DAC error
Internal hardware of master module or a connected
module
Restart the system and try to acknowledge the alarm.
If not possible please contact the manufacturer.
E.17
Parameter error
INTERLINK
Check if all INTERLINK cables are connected properly,
restart the system and try to acknowledge the alarm.
E.18
Sensor wire fault
ARC-DMOD-3SL module (CH1-3)
A sensor wire fault will be detected when configured
sensor is disconnected more than 5s.
It can be also detected in case when sensor is damaged,
broken or wrong type.
Check if the sensor is connected properly and try to
acknowledge the alarm.
In this case the sensor must be replaced with a new one
and the alarm can be acknowledged.
E.19
Sensor constellation error
ARC-DMOD-3SL module (CH1-3)
Unexpected sensor has been detected.
Sensor is connected on a position where it should not be
connected.
Position:
M.xx – xx = module number
S.yy – yy = sensor number
Disconnect the issued sensor and try to acknowledge
the alarm.
E.20
INTERLINK error
INTERLINK communication interface
Check if all INTERLINK cables are connected properly and
the RJ45 terminator on the last module has been placed
on OUT. Restart the system and try to acknowledge the
alarm.
E.21
INTERLINK constellation error
INTERLINK module missing or unexpected module
detected.
Wrong module type.
Example:
Point sensor module is connected instead of line sensor.
Check if all INTERLINK cables are connected properly and
the number/type of parameterized modules is correct.
Exchange the wrong device type or disconnect the added
module, restart the system and try to acknowledge the
alarm.
E.22
INTERLINK compatibility error
INTERLINK version of a module is not compatible with
version supported by master.
Replace the module with compatible firmware version.
E.24
UPF error
Software Master MAIN
User parameter file (UPF) missing or corrupted.
Also, it will be detected on each new produced Master
MAIN which is not yet configured.
Upload the UPF file from a parameter tool to the Master
MAIN.
The system will restart.
Then try to acknowledge the alarm.
E.25
MPF error
Internal software of master module
Restart the system and try to acknowledge the alarm.
If not possible please contact the manufacturer.
E.30
iCOM error
iCOM communication interface
Check if the iCOM cable is connected properly and the
RJ45 terminator on the external HMI has been placed
on OUT. Restart the system and try to acknowledge the
alarm
E.31
iCOM constellation error
iCOM HMI missing or unexpected HMI detected.
Check parameter P2185 and connect or disconnect HMI
accordingly.
E.32
iCOM compatibility error
iCOM version of the HMI is not compatible with version
supported by master.
Replace the HMI with compatible firmware version.
Troubleshooting alarms