ARCON 3G
ARCON 3G MANUAL
MN026015EN October 2020 www.eaton.com
Ss
Root
Subfolder
Parameter
Range
Description
Sensor 2
Disable / Enable
State of sensor 2
Sensor 3
Disable / Enable
State of sensor 3
Sensor 4
Disable / Enable
State of sensor 4
Sensor 5
Disable / Enable
State of sensor 5
Sensor 6
Disable / Enable
State of sensor 6
Section no. (Sensor 1)
1…32
Number of sections in which sensor 1 is placed
Section no. (Sensor 2)
1…32
Number of sections in which sensor 2 is placed
Section no. (Sensor 3)
1…32
Number of sections in which sensor 3 is placed
Section no. (Sensor 4)
1…32
Number of sections in which sensor 4 is placed
Section no. (Sensor 5)
1…32
Number of sections in which sensor 5 is placed
Section no. (Sensor 6)
1…32
Number of sections in which sensor 6 is placed
iCOM
Display 1
None / ARC-MAIN-HMI
Connected display on iCOM
Timeout screen saver
60…3600 s
After this time display turns off
IGNITION
PORT
Tripping module
None / ARC-TMOD-1QD
Connected Tripping module on IGNITION PORT
Section no. (Tripping
module)
1…32
Number of sections in which Tripping module is
placed
Section no. (ARC-AT)
1…32
Number of sections in which ARC-AT device is
placed
MASTERLINK
MASTERLINK
Disable / Enable
State of MASTERLINK function
Address
1…5
Master module address on MASTERLINK
Number of masters
2…5
Number of master modules connected on
MASTERLINK
Topology
Line / Ring
Master link network topology
CURRENT
MEAS.
Criteria di/dt
Disable / Enable
State of protection criteria di/dt
Limit I>>
0.5…5.0 x In
Setting for short circuit (multiple of nominal current)
NOMINALS
Nominal frequency
50Hz / 60Hz
Nominal frequency
VT - Primary
1…999999 V
Primary side value of voltage transformer
VT - Secondary
1…800 V
Secondary side value of voltage transformer
CT - Primary
1…65535 A
Primary side value of current transformer
CT - Secondary
1A / 5A
Secondary side value of current transformer
USER PROT.
MODE
Security
Disable / Enable
Enables user protected operation mode
Password
10000…99999
Password for user protected operation mode
Timeout
60…65535 s
Timeout for staying in the user protected
operation mode
Table 3 .5: Extended system – UPF parameters