14
ARCON 3G
ARCON 3G MANUAL
MN026015EN October 2020 www.eaton.com
The Simple system constellation contains of one Master LITE and up to 31 Detection
modules connected via INTERLINK communication. One Detection module supports 1
MLS sensor and up to 3 Line sensors.
The Simple system supports an easy configuration process without any programming or
parameter setting.
Features:
•
Stainless steel housing
•
Easy mounting on DIN rail TS35
•
Up to 31 light detection modules can be connected to the Master LITE via INTERLINK
communication
•
Up to 100m of INTERLINK distance between the Master LITE and the last connected
light detection module
•
Up to 93 Line Sensors (ARC-SL)
•
Up to 31 Mobile Light Sensors (ARC-SM) for enhanced personnel protection3 x
15-segment display
•
3 parallel operating fast binary tripping outputs (NO) with ≤ 2 ms tripping time
•
1 binary trip alarm output (NO) for indication
•
1 binary Watch Dog output (NC) for system supervision
•
No parameter setting required
Figure 2.1 Simple system – Block diagram
Simple system with ARC-LITE-3G Master