87
ARCON 3G
ARCON 3G MANUAL
MN026015EN October 2020 www.eaton.com
Description
Specification
Design
DIN rail TS35
Housing dimensions (W x H x D)
(193.04 x 91.44 x 76.20) mm
Weight
1.4kg
Installation position
Vertical
Protection type
IP20 (IEC 60529)
Table 5 .6: General technical data
Description
Specification
Power Supply
24V DC ±20 %
Power consumption max
< 25W. depending on configuration
External fuse
4A; “T-type”
Name of connector
-X1
Cross section
0,5 mm² … 2,5 mm²
Table 5 .7: Power supply
Description
Specification
INFO-Button
Get detailed information for an Error-Code shown in the STATUS-Display
ACK-Button
Acknowledge the currently displayed Error-Code shown in the STATUS-Display
Table 5 .8: Push Buttons
Outputs
TRIP outputs
Designation
Description
Specification*
TRIP 1
TRIP 2
TRIP 3
Rated voltage (AC)
Max. switching voltage
Continuous current
Max. making current
250V AC
300V AC/DC
16A AC/DC
16A AC/DC
Max. breaking capacity (AC)
Max. breaking capacity (DC)
for 24V
for 48V
for 60V
for 110V
for 220V
2000VA with cos
𝜑
> 0,8
For resistive load
16A
1,2A
0,8A
0,4A
0,3A
Contact switching times
Max. turn-on delay
Max. turn-off delay
< 1ms
5ms
Mechanical contact life-cycle
> 30 x 103 Operating cycles
Name of connector
-X3
Cross section
0,5 mm² … 2,5 mm²
* Environmental temperature: 25°C; humidity: non-condensing; device at steady operation at nominal values
Table 5 .9: Trip outputs
Alarm & Watchdog
Designation
Description
Specification*
TRIP ALARM
WATCHDOG
Rated voltage (AC)
Max. switching voltage
Continuous current
Max. making current
250V AC
300V AC/DC
16A AC/DC
16A AC/DC
Max. breaking capacity (AC)
Max. breaking capacity (DC)
for 24V
for 48V
for 60V
for 110V
for 220V
1500VA with cos
𝜑
> 0,8
For resistive load
6A
0,4A
0,3A
0,2A
0,15A
Contact switching times
Max. turn-on delay
Max. turn-off delay
12ms
5ms
Mechanical contact life-cycle
5 x 103 Operating cycles
Name of connector
-X3
Cross section
0,5 mm² … 2,5 mm²
* Environmental temperature: 25°C; humidity: non-condensing; device at steady operation at nominal values
Table 5 .10: Alarm & Watchdog
Indication LEDs
Status display
Designation
Color
Specification
SYSTEM
Green (1Hz)
Normal operation mode
Orange (2Hz)
Initialisation process started
TRIP
Red (2Hz)
Error occurred, see Error code table
and/or STATUS Display for detailed
information
Red
(steady)
ARC-Protection TRIP detected
Table 5 .11: Indications LEDs
Designation
Color
Specification
STATUS
Off
Normal operation mode
e.g.
“E.18”
Error code, see error code table for
detailed information
Table 5 .12: Status display
Proof 1 — October 29, 2020 3:00 PM