23
ARCON 3G
ARCON 3G MANUAL
MN026015EN October 2020 www.eaton.com
Detection module is connected via INTERLINK connection to master module.
The Detection module supports up to three Line Sensors (ARC-SL) and one Mobile
light sensor (ARC-SM).
For the case that sensors are enabled by parameter LEDs have following states:
Figure 2.8 Simple system – Detection module
The configuration process is an automated process of parameterization which includes
only using of internal HMI (segment display and buttons). To start configuration process,
follow the next steps:
1. Master LITE has to be de-energized.
2. Connect all modules and sensors which you want to use.
3. Press and hold the “ACK” button on the master module during powering up.
4. Release the button when you see that system LED blinking orange.
5. Acknowledge (by pressing the ACK button) detected number of:
a. L.xx (xx = Number of detected modules)
b. S.xx (xx = Number of detected sensors)
After acknowledging of detected modules and sensors by user, the Master LITE will
create and store the configuration file in non-volatile memory and it will restart. After
auto-restart, it will initialize constellation stored in the configuration file.
The configuration file will be permanently saved in non-volatile memory.
If the constellation should be changed, the configuration process must be
performed again.
ote:
N
The system doesn’t support any hot-plugging function!
Detection module
SYSTEM LED:
•
Orange
Not in operation
•
Red
System alarm
•
Green
In operation
•
Off
De-energized
SENSOR LED:
•
Orange
Wire fault
•
Red
Trip
•
Green
In operation
•
Off
Deactivated
Configuration process