![background image](http://html1.mh-extra.com/html/eaton/arcon-3g/arcon-3g_instructions-manual_3791809038.webp)
38
ARCON 3G
ARCON 3G MANUAL
MN026015EN October 2020 www.eaton.com
The Master MAIN supports connection of one Tripping module over the IGNITION PORT.
While Tripping module is in ready state the RUN LED blinks green at 1Hz and TRIP LED
is off. When Tripping module is not in ready state anymore then the RUN LED is turned
off as well. When a TRIP event occurs and at least the current criteria of one phase is
activated, the ignition command will be sent to the Tripping module. The TRIP LED will be
on and the RUN LED off. If only the light detecting criteria is activated for arc detection,
then the ignition command to the Tripping module will not be sent.
RUN LED:
Green 1Hz
Ready for ignition command
Off
NOT ready
TRIP LED:
Red
Trip state
Off
No trip
Figure 3.10 Extended system – Tripping module
Tripping module