ARCON 3G
ARCON 3G MANUAL
MN026015EN October 2020 www.eaton.com
Outputs
Ignition circuits
Indication LEDs
Designation
Description
Specification*
“L1/L2”
“L2/L3”
Rated Ignition voltage
30V DC
Ignition current:
t = 0 ms
t = 10 ms
≥ 9.5A
≥ 5.0A
Current for wire fault supervision
10mA
Max. turn-on delay
< 1µs
Name of connector
-X8
“LED RUN”
“GND”
“LED TRIP”
Functionality
For external indication LEDs
(same indication as ARC-AT)
Output voltage
depends on LED-type
Output current, max.
15 mA
Name of connector
-X8
Table 5 .35: Ignition circuits
Designation
Color
Specification
RUN
Green
(1Hz)
Normal operation mode
TRIP
Red
(steady)
ARC-Protection TRIP detected
Table 5 .36: Indication LEDs
Communication
IGNITION PORT
Data protocol
Description Specification
IGNITION PORT
IN
Interface:
RJ45 with CAT 6A cable
Location:
top of housing
Terminals:
“OUT“ (IGNITION PORT to the next
connected Tripping module)
Transmission distance:
max. 10m
Max. no. of modules connected to
IGNITION PORT
1 pc.
Table 5 .37: IGNITION PORT