92
ARCON 3G
ARCON 3G MANUAL
MN026015EN October 2020 www.eaton.com
Communication
Data protocol
Description
Specification*
INTERLINK
OUT
Interface:
RJ45 with CAT 6A cable
Location:
top of housing
Terminals:
“OUT“ (INTERLINK to the next
connected ARCON 3G module)*
Transmission distance:
max. 100m
Max. no. of modules connected to
INTERLINK
31 pcs.
* For failure-free operation use the included RJ45 terminator at the last INTERLINK connected module
Table 5 .23: INTERLINK
iCOM
MASTERLINK
INTERLINK
IGNITION PORT
USB interface
Data protocol
Description
Specification*
iCOM
OUT
Interface:
RJ45 with CAT 6A cable
Location:
top of housing
Terminals:
“OUT“ (iCOM to the next connected
HMI module)*
Transmission distance:
max. 40m
Max. no. of modules connected
to iCOM
1 pc.
* for failure-free operation use the included RJ45 terminator at the last iCOM connected module
Table 5 .25: iCOM
Data protocol
Description
Specification*
MASTERLINK
IN/OUT
Interface:
RJ45 with CAT 6A cable
Location:
front of housing
Terminals:
“IN“ & “OUT”
(MASTERLINK to the next connected
ARCON 3G Master module)
Transmission distance:
max. 100m
Max. no. of modules connected to
MASTERLINK
5 pcs.
Table 5 .24: MASTERLINK
Data protocol
Description
Specification*
IGNITION PORT
OUT
Interface:
RJ45 with CAT 6A cable
Location:
top of housing
Terminals:
“OUT“ (IGNITION PORT to the next
connected Tripping module)
Transmission distance:
max. 10m
Max. no. of modules connected to
IGNITION PORT
1 pc.
Data protocol
Description
Specification*
IGNITION PORT
OUT
Interface:
mini USB (standard)
Location:
front of housing
Terminals:
“USB”
Transmission distance:
max. 5m
Max. no. of modules connected
to USB
1 pc.
Table 5 .27: USB interface
IGNITION PORT must be connected properly, otherwise devices can get damaged! Only neces-
sary, if an external quenching device is considered for arc mitigation.
Table 5 .26: IGNITION PORT